ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0413016

Federal Type:

C

Water System Name:

CATHEDRAL VISTA WATER COMPANY

Primary Source:

GW

Principal County Served:

YAVAPAI

System Status:

A - MAP

Comments:

Activity Date:

1978-03-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
201309270124I 1074 ANTIMONY, TOTAL 2013-09-26 EPDS002 < MRL 0.001 MG/L .006 MG/L 2013-01-01
2015-12-31
201309270124I 1005 ARSENIC 2013-09-26 EPDS002 .0072  MG/L .01 MG/L 2013-01-01
2015-12-31
201309270124I 1010 BARIUM 2013-09-26 EPDS002 .21  MG/L 2 MG/L 2013-01-01
2015-12-31
201309270124I 1075 BERYLLIUM, TOTAL 2013-09-26 EPDS002 < MRL 0.001 MG/L .004 MG/L 2013-01-01
2015-12-31
201309270124I 1015 CADMIUM 2013-09-26 EPDS002 < MRL 0.0005 MG/L .005 MG/L 2013-01-01
2015-12-31
201309270124I 1020 CHROMIUM 2013-09-26 EPDS002 < MRL 0.001 MG/L .1 MG/L 2013-01-01
2015-12-31
201309270124I 1024 CYANIDE 2013-09-26 EPDS002 < MRL 0.025 MG/L .2 MG/L 2013-01-01
2015-12-31
201309270124I 1025 FLUORIDE 2013-09-26 EPDS002 .097  MG/L 4 MG/L 2013-01-01
2015-12-31
201309270124I 1035 MERCURY 2013-09-26 EPDS002 < MRL 0.0002 MG/L .002 MG/L 2013-01-01
2015-12-31
201309270124I 1036 NICKEL 2013-09-26 EPDS002 < MRL 0.005 MG/L 2013-01-01
2015-12-31
201309270124I 1040 NITRATE 2013-09-26 EPDS002 .66  MG/L 10 MG/L 2013-01-01
2013-12-31
201309270124I 1045 SELENIUM 2013-09-26 EPDS002 < MRL 0.005 MG/L .05 MG/L 2013-01-01
2015-12-31
201309270124I 1052 SODIUM 2013-09-26 EPDS002 7.6  MG/L 3000 MG/L 2013-01-01
2015-12-31
201309270124I 1085 THALLIUM, TOTAL 2013-09-26 EPDS002 < MRL 0.001 MG/L .002 MG/L 2013-01-01
2015-12-31