ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0412302

Federal Type:

NC

Water System Name:

AZ STATE PKS PATAGONIA LAKE

Primary Source:

GW

Principal County Served:

SANTA CRUZ

System Status:

A

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
46634 1005 ARSENIC 1996-04-02 EPDS001 < MRL 0.01 MG/L .01 MG/L
46634 1010 BARIUM 1996-04-02 EPDS001 .1  MG/L 2 MG/L
46634 1015 CADMIUM 1996-04-02 EPDS001 < MRL 0.001 MG/L .005 MG/L
46634 1017 CHLORIDE 1996-04-02 EPDS001 38.4  MG/L 250 MG/L
46634 1020 CHROMIUM 1996-04-02 EPDS001 < MRL 0.01 MG/L .1 MG/L
46634 1022 COPPER, FREE 1996-04-02 EPDS001 < MRL 0.01 MG/L 1.3 MG/L
46634 1025 FLUORIDE 1996-04-02 EPDS001 .24  MG/L 4 MG/L
46634 1028 IRON 1996-04-02 EPDS001 < MRL 0.1 MG/L .3 MG/L
46634 1030 LEAD 1996-04-02 EPDS001 < MRL 0.005 MG/L
46634 1032 MANGANESE 1996-04-02 EPDS001 < MRL 0.05 MG/L .05 MG/L
46634 1035 MERCURY 1996-04-02 EPDS001 < MRL 0.0005 MG/L .002 MG/L
46634 1040 NITRATE 1996-04-02 EPDS001 4.2  MG/L 10 MG/L
46634 1038 NITRATE-NITRITE 1996-04-02 EPDS001 4.2  MG/L 10 MG/L
46634 1041 NITRITE 1996-04-02 EPDS001 < MRL 0.1 MG/L 1 MG/L
46634 1045 SELENIUM 1996-04-02 EPDS001 < MRL 0.005 MG/L .05 MG/L
46634 1052 SODIUM 1996-04-02 EPDS001 100  MG/L 3000 MG/L
46634 1055 SULFATE 1996-04-02 EPDS001 273  MG/L 250 MG/L