ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0412006

Federal Type:

C

Water System Name:

PATAGONIA WATER DEPARTMENT

Primary Source:

GW

Principal County Served:

SANTA CRUZ

System Status:

A - MAP

Comments:

Activity Date:

1964-10-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
201608170290I 1074 ANTIMONY, TOTAL 2016-08-17 EPDS002 < MRL 0.001 MG/L .006 MG/L 2016-01-01
2018-12-31
201608170290I 1005 ARSENIC 2016-08-17 EPDS002 .002  MG/L .01 MG/L 2016-01-01
2018-12-31
201608170290I 1010 BARIUM 2016-08-17 EPDS002 .029  MG/L 2 MG/L 2016-01-01
2018-12-31
201608170290I 1075 BERYLLIUM, TOTAL 2016-08-17 EPDS002 < MRL 0.001 MG/L .004 MG/L 2016-01-01
2018-12-31
201608170290I 1015 CADMIUM 2016-08-17 EPDS002 < MRL 0.0005 MG/L .005 MG/L 2016-01-01
2018-12-31
201608170290I 1020 CHROMIUM 2016-08-17 EPDS002 < MRL 0.001 MG/L .1 MG/L 2016-01-01
2018-12-31
201608170290I 1024 CYANIDE 2016-08-17 EPDS002 < MRL 0.025 MG/L .2 MG/L 2016-01-01
2018-12-31
201608170290I 1025 FLUORIDE 2016-08-17 EPDS002 .45  MG/L 4 MG/L 2016-01-01
2018-12-31
201608170290I 1035 MERCURY 2016-08-17 EPDS002 < MRL 0.0002 MG/L .002 MG/L 2016-01-01
2018-12-31
201608170290I 1036 NICKEL 2016-08-17 EPDS002 .0063  MG/L 2016-01-01
2018-12-31
201608170290I 1040 NITRATE 2016-08-17 EPDS002 .69  MG/L 10 MG/L 2016-01-01
2016-12-31
201608170290I 1045 SELENIUM 2016-08-17 EPDS002 < MRL 0.005 MG/L .05 MG/L 2016-01-01
2018-12-31
201608170290I 1052 SODIUM 2016-08-17 EPDS002 21  MG/L 3000 MG/L 2016-01-01
2018-12-31
201608170290I 1085 THALLIUM, TOTAL 2016-08-17 EPDS002 < MRL 0.001 MG/L .002 MG/L 2016-01-01
2018-12-31