ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0412006

Federal Type:

C

Water System Name:

PATAGONIA WATER DEPARTMENT

Primary Source:

GW

Principal County Served:

SANTA CRUZ

System Status:

A - MAP

Comments:

Activity Date:

1964-10-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
18237-02 1005 ARSENIC 1993-11-04 EPDS001 < MRL 0.005 MG/L .01 MG/L
18237-02 1010 BARIUM 1993-11-04 EPDS001 .019  MG/L 2 MG/L
18237-02 1015 CADMIUM 1993-11-04 EPDS001 < MRL 0.007 MG/L .005 MG/L
18237-02 1017 CHLORIDE 1993-11-04 EPDS001 9.43  MG/L 250 MG/L
18237-02 1020 CHROMIUM 1993-11-04 EPDS001 < MRL 0.03 MG/L .1 MG/L
18237-02 1022 COPPER, FREE 1993-11-04 EPDS001 < MRL 0.003 MG/L 1.3 MG/L
18237-02 1025 FLUORIDE 1993-11-04 EPDS001 .45  MG/L 4 MG/L
18237-02 1028 IRON 1993-11-04 EPDS001 1.27  MG/L .3 MG/L
18237-02 1030 LEAD 1993-11-04 EPDS001 < MRL 0.002 MG/L
18237-02 1032 MANGANESE 1993-11-04 EPDS001 .011  MG/L .05 MG/L
18237-02 1035 MERCURY 1993-11-04 EPDS001 < MRL 0.0002 MG/L .002 MG/L
18237-02 1040 NITRATE 1993-11-04 EPDS001 1.22  MG/L 10 MG/L
18237-02 1041 NITRITE 1993-11-04 EPDS001 < MRL 0.002 MG/L 1 MG/L
18237-02 1045 SELENIUM 1993-11-04 EPDS001 < MRL 0.002 MG/L .05 MG/L
18237-02 1050 SILVER 1993-11-04 EPDS001 < MRL 0.013 MG/L .1 MG/L
18237-02 1052 SODIUM 1993-11-04 EPDS001 21  MG/L 3000 MG/L
18237-02 1055 SULFATE 1993-11-04 EPDS001 271  MG/L 250 MG/L
18237-02 1095 ZINC 1993-11-04 EPDS001 .16  MG/L 5 MG/L