Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
18237-01 1005 ARSENIC 1993-11-04 EPDS001 < MRL 0.005 MG/L .01 MG/L
18237-01 1010 BARIUM 1993-11-04 EPDS001 .021  MG/L 2 MG/L
18237-01 1015 CADMIUM 1993-11-04 EPDS001 < MRL 0.007 MG/L .005 MG/L
18237-01 1017 CHLORIDE 1993-11-04 EPDS001 6.87  MG/L 250 MG/L
18237-01 1020 CHROMIUM 1993-11-04 EPDS001 .013  MG/L .1 MG/L
18237-01 1022 COPPER, FREE 1993-11-04 EPDS001 < MRL 0.003 MG/L 1.3 MG/L
18237-01 1025 FLUORIDE 1993-11-04 EPDS001 .25  MG/L 4 MG/L
18237-01 1028 IRON 1993-11-04 EPDS001 .066  MG/L .3 MG/L
18237-01 1030 LEAD 1993-11-04 EPDS001 < MRL 0.002 MG/L
18237-01 1032 MANGANESE 1993-11-04 EPDS001 < MRL 0.01 MG/L .05 MG/L
18237-01 1035 MERCURY 1993-11-04 EPDS001 < MRL 0.0002 MG/L .002 MG/L
18237-01 1040 NITRATE 1993-11-04 EPDS001 1.95  MG/L 10 MG/L
18237-01 1041 NITRITE 1993-11-04 EPDS001 < MRL 0.002 MG/L 1 MG/L
18237-01 1045 SELENIUM 1993-11-04 EPDS001 < MRL 0.002 MG/L .05 MG/L
18237-01 1050 SILVER 1993-11-04 EPDS001 < MRL 0.013 MG/L .1 MG/L
18237-01 1052 SODIUM 1993-11-04 EPDS001 14  MG/L 3000 MG/L
18237-01 1055 SULFATE 1993-11-04 EPDS001 236  MG/L 250 MG/L
18237-01 1095 ZINC 1993-11-04 EPDS001 .04  MG/L 5 MG/L