ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0412004

Federal Type:

C

Water System Name:

NOGALES CITY OF

Primary Source:

GW

Principal County Served:

SANTA CRUZ

System Status:

A

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
15I0374-01(2I) 1074 ANTIMONY, TOTAL 2015-09-09 EPDS001 < MRL 0.0005 MG/L .006 MG/L 2015-01-01
2017-12-31
15I0374-01(2I) 1005 ARSENIC 2015-09-09 EPDS001 0.0023  MG/L .01 MG/L 2015-01-01
2017-12-31
15I0374-01(2I) 1010 BARIUM 2015-09-09 EPDS001 < MRL 0.05 MG/L 2 MG/L 2015-01-01
2017-12-31
15I0374-01(2I) 1075 BERYLLIUM, TOTAL 2015-09-09 EPDS001 < MDL 0.002 MG/L .004 MG/L 2015-01-01
2017-12-31
15I0374-01(2I) 1015 CADMIUM 2015-09-09 EPDS001 < MRL 0.002 MG/L .005 MG/L 2015-01-01
2017-12-31
15I0374-01(2I) 1020 CHROMIUM 2015-09-09 EPDS001 < MRL 0.03 MG/L .1 MG/L 2015-01-01
2017-12-31
15I0374-01(2I) 1024 CYANIDE 2015-09-09 EPDS001 < MDL 0.1 MG/L .2 MG/L 2015-01-01
2017-12-31
15I0374-01(2I) 1025 FLUORIDE 2015-09-09 EPDS001 < MDL 0.5 MG/L 4 MG/L 2015-01-01
2017-12-31
15I0374-01(2I) 1035 MERCURY 2015-09-09 EPDS001 < MDL 0.001 MG/L .002 MG/L 2015-01-01
2017-12-31
15I0374-01(2I) 1036 NICKEL 2015-09-09 EPDS001 < MDL 0.05 MG/L 2015-01-01
2017-12-31
15I0374-01(2I) 1045 SELENIUM 2015-09-09 EPDS001 < MRL 0.0025 MG/L .05 MG/L 2015-01-01
2017-12-31
15I0374-01(2I) 1052 SODIUM 2015-09-09 EPDS001 26  MG/L 3000 MG/L 2015-01-01
2017-12-31
15I0374-01(2I) 1085 THALLIUM, TOTAL 2015-09-09 EPDS001 < MRL 0.0005 MG/L .002 MG/L 2015-01-01
2017-12-31