ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0402106

Federal Type:

NP

Water System Name:

COUNTRY STORE

Primary Source:

GW

Principal County Served:

COCHISE

System Status:

I

Comments:

Activity Date:

2000-03-20



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
93-10-62141 1005 ARSENIC 1993-10-04 EPDS001 < MRL 0.005 MG/L .01 MG/L
93-10-62141 1010 BARIUM 1993-10-04 EPDS001 .2  MG/L 2 MG/L
93-10-62141 1015 CADMIUM 1993-10-04 EPDS001 < MRL 0.01 MG/L .005 MG/L
93-10-62141 1017 CHLORIDE 1993-10-04 EPDS001 32.5  MG/L 250 MG/L
93-10-62141 1020 CHROMIUM 1993-10-04 EPDS001 .02  MG/L .1 MG/L
93-10-62141 1022 COPPER, FREE 1993-10-04 EPDS001 < MRL 0.01 MG/L 1.3 MG/L
93-10-62141 1025 FLUORIDE 1993-10-04 EPDS001 .97  MG/L 4 MG/L
93-10-62141 1028 IRON 1993-10-04 EPDS001 .05  MG/L .3 MG/L
93-10-62141 1030 LEAD 1993-10-04 EPDS001 < MRL 0.001 MG/L
93-10-62141 1032 MANGANESE 1993-10-04 EPDS001 < MRL 0.01 MG/L .05 MG/L
93-10-62141 1035 MERCURY 1993-10-04 EPDS001 < MRL 0.0002 MG/L .002 MG/L
93-10-62141 1040 NITRATE 1993-10-04 EPDS001 .8  MG/L 10 MG/L
93-10-62141 1045 SELENIUM 1993-10-04 EPDS001 < MRL 0.005 MG/L .05 MG/L
93-10-62141 1050 SILVER 1993-10-04 EPDS001 < MRL 0.01 MG/L .1 MG/L
93-10-62141 1052 SODIUM 1993-10-04 EPDS001 44  MG/L 3000 MG/L
93-10-62141 1055 SULFATE 1993-10-04 EPDS001 41.3  MG/L 250 MG/L
93-10-62141 1095 ZINC 1993-10-04 EPDS001 .1  MG/L 5 MG/L