ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0411347

Federal Type:

NP

Water System Name:

BHP COPPER INC SAN MANUEL

Primary Source:

GW

Principal County Served:

PINAL

System Status:

I

Comments:

Activity Date:

2010-12-31



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
2612260271I 1074 ANTIMONY, TOTAL 2006-12-22 EPDS001 < MDL .006 MG/L 2003-01-01
2011-12-31
2612260271I 1005 ARSENIC 2006-12-22 EPDS001 .020  MG/L .01 MG/L
2612260271I 1010 BARIUM 2006-12-22 EPDS001 .021  MG/L 2 MG/L 2003-01-01
2011-12-31
2612260271I 1075 BERYLLIUM, TOTAL 2006-12-22 EPDS001 < MDL .004 MG/L 2003-01-01
2011-12-31
2612260271I 1015 CADMIUM 2006-12-22 EPDS001 < MDL .005 MG/L 2003-01-01
2011-12-31
2612260271I 1020 CHROMIUM 2006-12-22 EPDS001 .0091  MG/L .1 MG/L 2003-01-01
2011-12-31
2612260271I 1024 CYANIDE 2006-12-22 EPDS001 < MDL .2 MG/L 2003-01-01
2011-12-31
2612260271I 1025 FLUORIDE 2006-12-22 EPDS001 1.7  MG/L 4 MG/L
2612260271I 1035 MERCURY 2006-12-22 EPDS001 < MDL .002 MG/L 2003-01-01
2011-12-31
2612260271I 1036 NICKEL 2006-12-22 EPDS001 < MDL 2003-01-01
2011-12-31
2612260271I 1045 SELENIUM 2006-12-22 EPDS001 .0085  MG/L .05 MG/L 2003-01-01
2011-12-31
2612260271I 1052 SODIUM 2006-12-22 EPDS001 110  MG/L 3000 MG/L
2612260271I 1085 THALLIUM, TOTAL 2006-12-22 EPDS001 < MDL .002 MG/L 2003-01-01
2011-12-31