ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0411321

Federal Type:

C

Water System Name:

VILLA GRANDE DWID

Primary Source:

GW

Principal County Served:

PINAL

System Status:

A - MAP

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
0708567-01D 1074 ANTIMONY, TOTAL 2007-08-14 EPDS001 < MRL 0.002 MG/L .006 MG/L 2004-01-01
2012-12-31
0708567-01D 1005 ARSENIC 2007-08-14 EPDS001 .0036  MG/L .01 MG/L 2004-01-01
2012-12-31
0708567-01D 1010 BARIUM 2007-08-14 EPDS001 .0766  MG/L 2 MG/L 2004-01-01
2012-12-31
0708567-01D 1075 BERYLLIUM, TOTAL 2007-08-14 EPDS001 < MRL 0.0005 MG/L .004 MG/L 2004-01-01
2012-12-31
0708567-01D 1015 CADMIUM 2007-08-14 EPDS001 < MRL 0.002 MG/L .005 MG/L 2004-01-01
2012-12-31
0708567-01D 1020 CHROMIUM 2007-08-14 EPDS001 < MRL 0.005 MG/L .1 MG/L 2004-01-01
2012-12-31
0708567-01D 1025 FLUORIDE 2007-08-14 EPDS001 < MRL 0.5 MG/L 4 MG/L 2004-01-01
2012-12-31
0708567-01D 1036 NICKEL 2007-08-14 EPDS001 < MRL 0.005 MG/L 2004-01-01
2012-12-31
0708567-01D 1045 SELENIUM 2007-08-14 EPDS001 .0045  MG/L .05 MG/L 2004-01-01
2012-12-31
0708567-01D 1085 THALLIUM, TOTAL 2007-08-14 EPDS001 < MRL 0.0005 MG/L .002 MG/L 2004-01-01
2012-12-31