ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0411131

Federal Type:

C

Water System Name:

GWR - SANTA CRUZ WATER CO. INC.

Primary Source:

GW

Principal County Served:

PINAL

System Status:

A

Comments:

Activity Date:

2002-03-20



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
550-141863-2 1005 ARSENIC 2020-05-07 EPDS002 0.0070  MG/L .01 MG/L 2018-01-01
2020-12-31
550-141863-2 4006 COMBINED URANIUM 2020-05-07 EPDS002 3.2  UG/L 30 UG/L 2020-01-01
2025-12-31
550-141863-2 1025 FLUORIDE 2020-05-07 EPDS002 0.75  MG/L 4 MG/L 2018-01-01
2020-12-31
550-141863-2 1040 NITRATE 2020-05-07 EPDS002 5.2  MG/L 10 MG/L 2020-04-01
2020-06-30