ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0411128

Federal Type:

C

Water System Name:

EPCOR - SAN TAN

Primary Source:

GW

Principal County Served:

PINAL

System Status:

A

Comments:

Activity Date:

1999-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
121702-07I 1074 ANTIMONY, TOTAL 2002-12-16 EPDS007 < MRL 0.003 MG/L .006 MG/L 2002-01-01
2010-12-31
121702-07I 1005 ARSENIC 2002-12-16 EPDS007 .0095  MG/L .01 MG/L 2002-01-01
2010-12-31
121702-07I 1010 BARIUM 2002-12-16 EPDS007 < MRL 0.01 MG/L 2 MG/L 2002-01-01
2010-12-31
121702-07I 1075 BERYLLIUM, TOTAL 2002-12-16 EPDS007 < MRL 0.0005 MG/L .004 MG/L 2002-01-01
2010-12-31
121702-07I 1015 CADMIUM 2002-12-16 EPDS007 < MRL 0.0005 MG/L .005 MG/L 2002-01-01
2010-12-31
121702-07I 1020 CHROMIUM 2002-12-16 EPDS007 < MRL 0.01 MG/L .1 MG/L 2002-01-01
2010-12-31
121702-07I 1024 CYANIDE 2002-12-16 EPDS007 < MRL 0.005 MG/L .2 MG/L 2002-01-01
2010-12-31
121702-07I 1025 FLUORIDE 2002-12-16 EPDS007 .67  MG/L 4 MG/L 2002-01-01
2010-12-31
121702-07I 1035 MERCURY 2002-12-16 EPDS007 < MRL 0.0002 MG/L .002 MG/L 2002-01-01
2010-12-31
121702-07I 1036 NICKEL 2002-12-16 EPDS007 < MRL 0.01 MG/L 2002-01-01
2010-12-31
121702-07I 1041 NITRITE 2002-12-16 EPDS007 < MRL 0.01 MG/L 1 MG/L 2002-01-01
2010-12-31
121702-07I 1045 SELENIUM 2002-12-16 EPDS007 < MRL 0.003 MG/L .05 MG/L 2002-01-01
2010-12-31
121702-07I 1052 SODIUM 2002-12-16 EPDS007 180  MG/L 3000 MG/L 2002-01-01
2010-12-31
121702-07I 1085 THALLIUM, TOTAL 2002-12-16 EPDS007 < MRL 0.001 MG/L .002 MG/L 2002-01-01
2010-12-31