ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0411128

Federal Type:

C

Water System Name:

EPCOR - SAN TAN

Primary Source:

GW

Principal County Served:

PINAL

System Status:

A

Comments:

Activity Date:

1999-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
201201240130I 1074 ANTIMONY, TOTAL 2012-01-23 EPDS005 < MRL 0.001 MG/L .006 MG/L 2012-01-01
2014-12-31
201201240130I 1005 ARSENIC 2012-01-23 EPDS005 0.0036  MG/L .01 MG/L 2012-01-01
2014-12-31
201201240130I 1010 BARIUM 2012-01-23 EPDS005 0.050  MG/L 2 MG/L 2012-01-01
2014-12-31
201201240130I 1075 BERYLLIUM, TOTAL 2012-01-23 EPDS005 < MRL 0.001 MG/L .004 MG/L 2012-01-01
2014-12-31
201201240130I 1015 CADMIUM 2012-01-23 EPDS005 < MRL 0.0005 MG/L .005 MG/L 2012-01-01
2014-12-31
201201240130I 1020 CHROMIUM 2012-01-23 EPDS005 0.0031  MG/L .1 MG/L 2012-01-01
2014-12-31
201201240130I 1024 CYANIDE 2012-01-23 EPDS005 < MRL 0.025 MG/L .2 MG/L 2012-01-01
2014-12-31
201201240130I 1025 FLUORIDE 2012-01-23 EPDS005 0.31  MG/L 4 MG/L 2012-01-01
2014-12-31
201201240130I 1035 MERCURY 2012-01-23 EPDS005 < MRL 0.0002 MG/L .002 MG/L 2012-01-01
2014-12-31
201201240130I 1036 NICKEL 2012-01-23 EPDS005 < MRL 0.005 MG/L 2012-01-01
2014-12-31
201201240130I 1045 SELENIUM 2012-01-23 EPDS005 < MRL 0.005 MG/L .05 MG/L 2012-01-01
2014-12-31
201201240130I 1052 SODIUM 2012-01-23 EPDS005 130  MG/L 3000 MG/L 2012-01-01
2014-12-31
201201240130I 1085 THALLIUM, TOTAL 2012-01-23 EPDS005 < MRL 0.001 MG/L .002 MG/L 2012-01-01
2014-12-31