Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
202004240031I 1074 ANTIMONY, TOTAL 2020-04-23 EPDS139 < MRL 1 UG/L .006 MG/L 2020-01-01
2022-12-31
202004240031I 1005 ARSENIC 2020-04-23 EPDS139 5.5  UG/L .01 MG/L 2020-01-01
2022-12-31
202004240031I 1010 BARIUM 2020-04-23 EPDS139 46  UG/L 2 MG/L 2020-01-01
2022-12-31
202004240031I 1075 BERYLLIUM, TOTAL 2020-04-23 EPDS139 < MRL 1 UG/L .004 MG/L 2020-01-01
2022-12-31
202004240031I 1015 CADMIUM 2020-04-23 EPDS139 < MRL 0.5 UG/L .005 MG/L 2020-01-01
2022-12-31
202004240031I 1020 CHROMIUM 2020-04-23 EPDS139 2.5  UG/L .1 MG/L 2020-01-01
2022-12-31
202004240031I 1024 CYANIDE 2020-04-23 EPDS139 < MRL 0.025 MG/L .2 MG/L 2020-01-01
2022-12-31
202004240031I 1025 FLUORIDE 2020-04-23 EPDS139 0.36  MG/L 4 MG/L 2020-01-01
2022-12-31
202004240031I 1035 MERCURY 2020-04-23 EPDS139 < MRL 0.2 UG/L .002 MG/L 2020-01-01
2022-12-31
202004240031I 1036 NICKEL 2020-04-23 EPDS139 < MRL 5 UG/L 2020-01-01
2022-12-31
202004240031I 1040 NITRATE 2020-04-23 EPDS139 5.7  MG/L 10 MG/L 2020-01-01
2020-12-31
202004240031I 1038 NITRATE-NITRITE 2020-04-23 EPDS139 5.7  MG/L 10 MG/L
202004240031I 1041 NITRITE 2020-04-23 EPDS139 < MRL 0.05 MG/L 1 MG/L 2020-01-01
2028-12-31
202004240031I 1045 SELENIUM 2020-04-23 EPDS139 < MRL 5 UG/L .05 MG/L 2020-01-01
2022-12-31
202004240031I 1052 SODIUM 2020-04-23 EPDS139 150  MG/L 3000 MG/L 2020-01-01
2022-12-31
202004240031I 1085 THALLIUM, TOTAL 2020-04-23 EPDS139 < MRL 1 UG/L .002 MG/L 2020-01-01
2022-12-31