Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
BC-01158 1074 ANTIMONY, TOTAL 1997-02-10 EPDS001 < MRL 0.003 MG/L .006 MG/L
BC-01158 1005 ARSENIC 1997-02-10 EPDS001 .028  MG/L .01 MG/L
BC-01158 1010 BARIUM 1997-02-10 EPDS001 < MRL 0.01 MG/L 2 MG/L
BC-01158 1075 BERYLLIUM, TOTAL 1997-02-10 EPDS001 < MRL 0.002 MG/L .004 MG/L
BC-01158 1015 CADMIUM 1997-02-10 EPDS001 < MRL 0.005 MG/L .005 MG/L
BC-01158 1020 CHROMIUM 1997-02-10 EPDS001 < MRL 0.05 MG/L .1 MG/L
BC-01158 1024 CYANIDE 1997-02-10 EPDS001 < MRL 0.01 MG/L .2 MG/L
BC-01158 1025 FLUORIDE 1997-02-10 EPDS001 4.9  MG/L 4 MG/L
BC-01158 1035 MERCURY 1997-02-10 EPDS001 < MRL 0.0002 MG/L .002 MG/L
BC-01158 1036 NICKEL 1997-02-10 EPDS001 < MRL 0.01 MG/L
BC-01158 1040 NITRATE 1997-02-10 EPDS001 3.05  MG/L 10 MG/L
BC-01158 1045 SELENIUM 1997-02-10 EPDS001 < MRL 0.005 MG/L .05 MG/L
BC-01158 1052 SODIUM 1997-02-10 EPDS001 182  MG/L 3000 MG/L
BC-01158 1055 SULFATE 1997-02-10 EPDS001 115  MG/L 250 MG/L
BC-01158 1085 THALLIUM, TOTAL 1997-02-10 EPDS001 .0018  MG/L .002 MG/L