ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0411085

Federal Type:

NTNC

Water System Name:

NISSAN TECHNICAL CENTER

Primary Source:

GW

Principal County Served:

PINAL

System Status:

A - MAP

Comments:

Activity Date:

1992-07-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
ISH0989-01I 1074 ANTIMONY, TOTAL 2009-08-11 EPDS001 < MRL 0.002 MG/L .006 MG/L 2003-01-01
2011-12-31
ISH0989-01I 1005 ARSENIC 2009-08-11 EPDS001 .036  MG/L .01 MG/L 2003-01-01
2011-12-31
ISH0989-01I 1010 BARIUM 2009-08-11 EPDS001 .0023  MG/L 2 MG/L 2003-01-01
2011-12-31
ISH0989-01I 1075 BERYLLIUM, TOTAL 2009-08-11 EPDS001 < MRL 0.0005 MG/L .004 MG/L 2003-01-01
2011-12-31
ISH0989-01I 1015 CADMIUM 2009-08-11 EPDS001 < MRL 0.001 MG/L .005 MG/L 2003-01-01
2011-12-31
ISH0989-01I 1020 CHROMIUM 2009-08-11 EPDS001 .03  MG/L .1 MG/L 2003-01-01
2011-12-31
ISH0989-01I 1024 CYANIDE 2009-08-11 EPDS001 < MRL 0.02 MG/L .2 MG/L 2003-01-01
2011-12-31
ISH0989-01I 1035 MERCURY 2009-08-11 EPDS001 < MRL 0.0002 MG/L .002 MG/L 2003-01-01
2011-12-31
ISH0989-01I 1036 NICKEL 2009-08-11 EPDS001 < MRL 0.002 MG/L 2003-01-01
2011-12-31
ISH0989-01I 1045 SELENIUM 2009-08-11 EPDS001 < MRL 0.002 MG/L .05 MG/L 2003-01-01
2011-12-31
ISH0989-01I 1085 THALLIUM, TOTAL 2009-08-11 EPDS001 < MDL 0.001 MG/L .002 MG/L 2003-01-01
2011-12-31