ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0411079

Federal Type:

C

Water System Name:

SIGNAL PEAK WATER COMPANY

Primary Source:

GWP

Principal County Served:

PINAL

System Status:

A

Comments:

Activity Date:

1976-01-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
92-WA-4821 1005 ARSENIC 1992-04-29 EPDS001 < MRL 0.005 MG/L .01 MG/L
92-WA-4821 1010 BARIUM 1992-04-29 EPDS001 < MRL 0.1 MG/L 2 MG/L
92-WA-4821 1015 CADMIUM 1992-04-29 EPDS001 < MRL 0.005 MG/L .005 MG/L
92-WA-4821 1017 CHLORIDE 1992-04-29 EPDS001 488  MG/L 250 MG/L
92-WA-4821 1020 CHROMIUM 1992-04-29 EPDS001 < MRL 0.01 MG/L .1 MG/L
92-WA-4821 1022 COPPER, FREE 1992-04-29 EPDS001 < MRL 0.01 MG/L 1.3 MG/L
92-WA-4821 1025 FLUORIDE 1992-04-29 EPDS001 .84  MG/L 4 MG/L
92-WA-4821 1028 IRON 1992-04-29 EPDS001 .067  MG/L .3 MG/L
92-WA-4821 1030 LEAD 1992-04-29 EPDS001 < MRL 0.01 MG/L
92-WA-4821 1032 MANGANESE 1992-04-29 EPDS001 .012  MG/L .05 MG/L
92-WA-4821 1035 MERCURY 1992-04-29 EPDS001 < MRL 0.001 MG/L .002 MG/L
92-WA-4821 1040 NITRATE 1992-04-29 EPDS001 15.7  MG/L 10 MG/L
92-WA-4821 1045 SELENIUM 1992-04-29 EPDS001 < MRL 0.005 MG/L .05 MG/L
92-WA-4821 1050 SILVER 1992-04-29 EPDS001 < MRL 0.01 MG/L .1 MG/L
92-WA-4821 1052 SODIUM 1992-04-29 EPDS001 210  MG/L 3000 MG/L
92-WA-4821 1055 SULFATE 1992-04-29 EPDS001 720  MG/L 250 MG/L
92-WA-4821 1095 ZINC 1992-04-29 EPDS001 5.78  MG/L 5 MG/L