ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0411044

Federal Type:

C

Water System Name:

QUEEN VALLEY DWID

Primary Source:

GW

Principal County Served:

PINAL

System Status:

A - MAP

Comments:

Activity Date:

1978-03-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
BC-01311 1074 ANTIMONY, TOTAL 1997-02-18 EPDS001 < MRL 0.003 MG/L .006 MG/L
BC-01311 1005 ARSENIC 1997-02-18 EPDS001 < MRL 0.005 MG/L .01 MG/L
BC-01311 1010 BARIUM 1997-02-18 EPDS001 .04  MG/L 2 MG/L
BC-01311 1075 BERYLLIUM, TOTAL 1997-02-18 EPDS001 < MRL 0.002 MG/L .004 MG/L
BC-01311 1015 CADMIUM 1997-02-18 EPDS001 < MRL 0.002 MG/L .005 MG/L
BC-01311 1020 CHROMIUM 1997-02-18 EPDS001 < MRL 0.01 MG/L .1 MG/L
BC-01311 1024 CYANIDE 1997-02-18 EPDS001 < MRL 0.01 MG/L .2 MG/L
BC-01311 1025 FLUORIDE 1997-02-18 EPDS001 .6  MG/L 4 MG/L
BC-01311 1035 MERCURY 1997-02-18 EPDS001 < MRL 0.0002 MG/L .002 MG/L
BC-01311 1036 NICKEL 1997-02-18 EPDS001 .01  MG/L
BC-01311 1040 NITRATE 1997-02-18 EPDS001 1.28  MG/L 10 MG/L
BC-01311 1045 SELENIUM 1997-02-18 EPDS001 < MRL 0.005 MG/L .05 MG/L
BC-01311 1052 SODIUM 1997-02-18 EPDS001 49.4  MG/L 3000 MG/L
BC-01311 1055 SULFATE 1997-02-18 EPDS001 555  MG/L 250 MG/L
BC-01311 1085 THALLIUM, TOTAL 1997-02-18 EPDS001 < MRL 0.001 MG/L .002 MG/L