ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0411036

Federal Type:

C

Water System Name:

MARICOPA CONSOLIDATED DWID

Primary Source:

GW

Principal County Served:

PINAL

System Status:

A - MAP

Comments:

Activity Date:

1954-12-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
201809280374I 1074 ANTIMONY, TOTAL 2018-09-28 EPDS003 < MRL 1 UG/L .006 MG/L 2018-01-01
2020-12-31
201809280374I 1005 ARSENIC 2018-09-28 EPDS003 8.7  UG/L .01 MG/L 2018-07-01
2018-09-30
201809280374I 1010 BARIUM 2018-09-28 EPDS003 91  UG/L 2 MG/L 2018-01-01
2020-12-31
201809280374I 1075 BERYLLIUM, TOTAL 2018-09-28 EPDS003 < MRL 1 UG/L .004 MG/L 2018-01-01
2020-12-31
201809280374I 1015 CADMIUM 2018-09-28 EPDS003 < MRL 0.5 UG/L .005 MG/L 2018-01-01
2020-12-31
201809280374I 1020 CHROMIUM 2018-09-28 EPDS003 4.8  UG/L .1 MG/L 2018-01-01
2020-12-31
201809280374I 1024 CYANIDE 2018-09-28 EPDS003 < MRL 0.025 MG/L .2 MG/L 2018-01-01
2020-12-31
201809280374I 1025 FLUORIDE 2018-09-28 EPDS003 2.2  MG/L 4 MG/L 2018-01-01
2020-12-31
201809280374I 1035 MERCURY 2018-09-28 EPDS003 < MRL 0.2 UG/L .002 MG/L 2018-01-01
2020-12-31
201809280374I 1036 NICKEL 2018-09-28 EPDS003 < MRL 5 UG/L 2018-01-01
2020-12-31
201809280374I 1040 NITRATE 2018-09-28 EPDS003 5.3  MG/L 10 MG/L 2018-01-01
2018-12-31
201809280374I 1045 SELENIUM 2018-09-28 EPDS003 7.5  UG/L .05 MG/L 2018-01-01
2020-12-31
201809280374I 1052 SODIUM 2018-09-28 EPDS003 150  MG/L 3000 MG/L 2018-01-01
2020-12-31
201809280374I 1085 THALLIUM, TOTAL 2018-09-28 EPDS003 < MRL 1 UG/L .002 MG/L 2018-01-01
2020-12-31