Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
L94-2326 1005 ARSENIC 1994-07-13 XEPDS001 < MRL 0.005 MG/L .01 MG/L
L94-2326 1010 BARIUM 1994-07-13 XEPDS001 < MRL 0.1 MG/L 2 MG/L
L94-2326 1015 CADMIUM 1994-07-13 XEPDS001 < MRL 0.005 MG/L .005 MG/L
L94-2326 1017 CHLORIDE 1994-07-13 XEPDS001 212  MG/L 250 MG/L
L94-2326 1020 CHROMIUM 1994-07-13 XEPDS001 < MRL 0.01 MG/L .1 MG/L
L94-2326 1022 COPPER, FREE 1994-07-13 XEPDS001 < MRL 0.01 MG/L 1.3 MG/L
L94-2326 1025 FLUORIDE 1994-07-13 XEPDS001 1.49  MG/L 4 MG/L
L94-2326 1028 IRON 1994-07-13 XEPDS001 .03  MG/L .3 MG/L
L94-2326 1030 LEAD 1994-07-13 XEPDS001 < MRL 0.005 MG/L
L94-2326 1032 MANGANESE 1994-07-13 XEPDS001 < MRL 0.01 MG/L .05 MG/L
L94-2326 1035 MERCURY 1994-07-13 XEPDS001 < MRL 0.001 MG/L .002 MG/L
L94-2326 1040 NITRATE 1994-07-13 XEPDS001 3.93  MG/L 10 MG/L
L94-2326 1045 SELENIUM 1994-07-13 XEPDS001 < MRL 0.005 MG/L .05 MG/L
L94-2326 1050 SILVER 1994-07-13 XEPDS001 < MRL 0.01 MG/L .1 MG/L
L94-2326 1052 SODIUM 1994-07-13 XEPDS001 95.9  MG/L 3000 MG/L
L94-2326 1055 SULFATE 1994-07-13 XEPDS001 78  MG/L 250 MG/L