ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0410357

Federal Type:

C

Water System Name:

METROPOLITAN DWID - DIABLO VILLAGE

Primary Source:

GW

Principal County Served:

PIMA

System Status:

A - MAP

Comments:

Activity Date:

2002-10-02



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
PTB1106-02 1074 ANTIMONY, TOTAL 2010-02-17 EPDS001 < MRL 0.003 MG/L .006 MG/L 2010-01-01
2012-12-31
PTB1106-02 1010 BARIUM 2010-02-17 EPDS001 .029  MG/L 2 MG/L 2010-01-01
2012-12-31
PTB1106-02 1075 BERYLLIUM, TOTAL 2010-02-17 EPDS001 < MRL 0.001 MG/L .004 MG/L 2010-01-01
2012-12-31
PTB1106-02 1015 CADMIUM 2010-02-17 EPDS001 < MRL 0.001 MG/L .005 MG/L 2010-01-01
2012-12-31
PTB1106-02 1020 CHROMIUM 2010-02-17 EPDS001 .0024  MG/L .1 MG/L 2010-01-01
2012-12-31
PTB1106-02 1024 CYANIDE 2010-02-17 EPDS001 < MRL 0.005 MG/L .2 MG/L 2010-01-01
2012-12-31
PTB1106-02 1025 FLUORIDE 2010-02-17 EPDS001 .48  MG/L 4 MG/L 2010-01-01
2012-12-31
PTB1106-02 1035 MERCURY 2010-02-17 EPDS001 < MRL 0.0002 MG/L .002 MG/L 2010-01-01
2012-12-31
PTB1106-02 1036 NICKEL 2010-02-17 EPDS001 < MRL 0.01 MG/L 2010-01-01
2012-12-31
PTB1106-02 1040 NITRATE 2010-02-17 EPDS001 1.9  MG/L 10 MG/L 2010-01-01
2010-12-31
PTB1106-02 1038 NITRATE-NITRITE 2010-02-17 EPDS001 1.9  MG/L 10 MG/L
PTB1106-02 1041 NITRITE 2010-02-17 EPDS001 < MRL 0.2 MG/L 1 MG/L 2004-01-01
2012-12-31
PTB1106-02 1045 SELENIUM 2010-02-17 EPDS001 < MRL 0.002 MG/L .05 MG/L 2010-01-01
2012-12-31
PTB1106-02 1052 SODIUM 2010-02-17 EPDS001 70  MG/L 3000 MG/L 2010-01-01
2012-12-31
PTB1106-02 1085 THALLIUM, TOTAL 2010-02-17 EPDS001 < MRL 0.001 MG/L .002 MG/L 2010-01-01
2012-12-31