ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0410354

Federal Type:

C

Water System Name:

ANWAY MANVILLE WATER COMPANY

Primary Source:

GW

Principal County Served:

PIMA

System Status:

A - MAP

Comments:

Activity Date:

1998-01-30



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
201707240405I 1074 ANTIMONY, TOTAL 2017-07-24 EPDS002 < MRL 1 UG/L .006 MG/L 2017-01-01
2025-12-31
201707240405I 1005 ARSENIC 2017-07-24 EPDS002 2.9  UG/L .01 MG/L 2017-01-01
2025-12-31
201707240405I 1010 BARIUM 2017-07-24 EPDS002 70.00  UG/L 2 MG/L 2017-01-01
2025-12-31
201707240405I 1075 BERYLLIUM, TOTAL 2017-07-24 EPDS002 < MRL 1 UG/L .004 MG/L 2017-01-01
2025-12-31
201707240405I 1015 CADMIUM 2017-07-24 EPDS002 < MRL 0.5 UG/L .005 MG/L 2017-01-01
2025-12-31
201707240405I 1020 CHROMIUM 2017-07-24 EPDS002 2.7  UG/L .1 MG/L 2017-01-01
2025-12-31
201707240405I 1024 CYANIDE 2017-07-24 EPDS002 < MRL 0.025 MG/L .2 MG/L 2017-01-01
2025-12-31
201707240405I 1025 FLUORIDE 2017-07-24 EPDS002 0.54  MG/L 4 MG/L 2017-01-01
2025-12-31
201707240405I 1035 MERCURY 2017-07-24 EPDS002 < MRL 0.2 UG/L .002 MG/L 2017-01-01
2025-12-31
201707240405I 1036 NICKEL 2017-07-24 EPDS002 < MRL 5 UG/L 2017-01-01
2025-12-31
201707240405I 1040 NITRATE 2017-07-24 EPDS002 3.2  MG/L 10 MG/L 2017-01-01
2017-12-31
201707240405I 1045 SELENIUM 2017-07-24 EPDS002 < MRL 5 UG/L .05 MG/L 2017-01-01
2025-12-31
201707240405I 1052 SODIUM 2017-07-24 EPDS002 44.00  MG/L 3000 MG/L 2017-01-01
2025-12-31
201707240405I 1085 THALLIUM, TOTAL 2017-07-24 EPDS002 < MRL 1 UG/L .002 MG/L 2017-01-01
2025-12-31