ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0410270

Federal Type:

C

Water System Name:

TUCSON WATER SIERRITA FOOTHILLS

Primary Source:

GW

Principal County Served:

PIMA

System Status:

A - MAP

Comments:

Activity Date:

1991-04-24



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
201004150122I 1074 ANTIMONY, TOTAL 2010-04-14 EPDS270 < MRL 0.001 MG/L .006 MG/L 2010-01-01
2018-12-31
201004150122I 1005 ARSENIC 2010-04-14 EPDS270 0.0053  MG/L .01 MG/L 2010-01-01
2018-12-31
201004150122I 1010 BARIUM 2010-04-14 EPDS270 0.016  MG/L 2 MG/L 2010-01-01
2018-12-31
201004150122I 1075 BERYLLIUM, TOTAL 2010-04-14 EPDS270 < MRL 0.001 MG/L .004 MG/L 2010-01-01
2018-12-31
201004150122I 1015 CADMIUM 2010-04-14 EPDS270 < MRL 0.0005 MG/L .005 MG/L 2010-01-01
2018-12-31
201004150122I 1020 CHROMIUM 2010-04-14 EPDS270 0.003  MG/L .1 MG/L 2010-01-01
2018-12-31
201004150122I 1024 CYANIDE 2010-04-14 EPDS270 < MRL 0.005 MG/L .2 MG/L 2010-01-01
2018-12-31
201004150122I 1025 FLUORIDE 2010-04-14 EPDS270 0.58  MG/L 4 MG/L 2010-01-01
2018-12-31
201004150122I 1035 MERCURY 2010-04-14 EPDS270 < MRL 0.0002 MG/L .002 MG/L 2010-01-01
2018-12-31
201004150122I 1036 NICKEL 2010-04-14 EPDS270 < MRL 0.005 MG/L 2010-01-01
2018-12-31
201004150122I 1040 NITRATE 2010-04-14 EPDS270 1.7  MG/L 10 MG/L 2010-01-01
2010-12-31
201004150122I 1045 SELENIUM 2010-04-14 EPDS270 < MRL 0.005 MG/L .05 MG/L 2010-01-01
2018-12-31
201004150122I 1052 SODIUM 2010-04-14 EPDS270 34  MG/L 3000 MG/L 2010-01-01
2018-12-31
201004150122I 1085 THALLIUM, TOTAL 2010-04-14 EPDS270 < MRL 0.001 MG/L .002 MG/L 2010-01-01
2018-12-31