ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0410175

Federal Type:

C

Water System Name:

ORO VALLEY WATER COUNTRYSIDE

Primary Source:

GW

Principal County Served:

PIMA

System Status:

A - MAP

Comments:

Activity Date:

1981-09-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
T95-44025-I 1074 ANTIMONY, TOTAL 1995-12-18 EPDS001 < MRL 0.005 MG/L .006 MG/L
T95-44025-I 1005 ARSENIC 1995-12-18 EPDS001 < MRL 0.005 MG/L .01 MG/L
T95-44025-I 1010 BARIUM 1995-12-18 EPDS001 < MRL 1 MG/L 2 MG/L
T95-44025-I 1075 BERYLLIUM, TOTAL 1995-12-18 EPDS001 < MRL 0.003 MG/L .004 MG/L
T95-44025-I 1015 CADMIUM 1995-12-18 EPDS001 < MRL 0.003 MG/L .005 MG/L
T95-44025-I 1020 CHROMIUM 1995-12-18 EPDS001 < MRL 0.03 MG/L .1 MG/L
T95-44025-I 1022 COPPER, FREE 1995-12-18 EPDS001 < MRL 0.02 MG/L 1.3 MG/L
T95-44025-I 1024 CYANIDE 1995-12-18 EPDS001 < MRL 0.1 MG/L .2 MG/L
T95-44025-I 1025 FLUORIDE 1995-12-18 EPDS001 < MRL 0.5 MG/L 4 MG/L
T95-44025-I 1028 IRON 1995-12-18 EPDS001 < MRL 0.1 MG/L .3 MG/L
T95-44025-I 1030 LEAD 1995-12-18 EPDS001 < MRL 0.005 MG/L
T95-44025-I 1032 MANGANESE 1995-12-18 EPDS001 < MRL 0.02 MG/L .05 MG/L
T95-44025-I 1035 MERCURY 1995-12-18 EPDS001 < MRL 0.001 MG/L .002 MG/L
T95-44025-I 1036 NICKEL 1995-12-18 EPDS001 < MRL 0.1 MG/L
T95-44025-I 1040 NITRATE 1995-12-18 EPDS001 1  MG/L 10 MG/L
T95-44025-I 1041 NITRITE 1995-12-18 EPDS001 < MRL 0.1 MG/L 1 MG/L
T95-44025-I 1045 SELENIUM 1995-12-18 EPDS001 < MRL 0.005 MG/L .05 MG/L
T95-44025-I 1050 SILVER 1995-12-18 EPDS001 < MRL 0.01 MG/L .1 MG/L
T95-44025-I 1052 SODIUM 1995-12-18 EPDS001 30.1  MG/L 3000 MG/L
T95-44025-I 1085 THALLIUM, TOTAL 1995-12-18 EPDS001 < MRL 0.005 MG/L .002 MG/L
T95-44025-I 1095 ZINC 1995-12-18 EPDS001 < MRL 0.04 MG/L 5 MG/L