ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0402044

Federal Type:

C

Water System Name:

PUEBLO DEL SOL WATER COMPANY

Primary Source:

GW

Principal County Served:

COCHISE

System Status:

A

Comments:

Activity Date:

1973-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
6092563-01I 1074 ANTIMONY, TOTAL 2016-09-29 EPDS002 < MRL 0.0005 MG/L .006 MG/L 2016-01-01
2018-12-31
6092563-01I 1005 ARSENIC 2016-09-29 EPDS002 < MRL 0.001 MG/L .01 MG/L 2016-01-01
2018-12-31
6092563-01I 1010 BARIUM 2016-09-29 EPDS002 .05  MG/L 2 MG/L 2016-01-01
2018-12-31
6092563-01I 1075 BERYLLIUM, TOTAL 2016-09-29 EPDS002 < MRL 0.002 MG/L .004 MG/L 2016-01-01
2018-12-31
6092563-01I 1015 CADMIUM 2016-09-29 EPDS002 < MRL 0.0001 MG/L .005 MG/L 2016-01-01
2018-12-31
6092563-01I 1020 CHROMIUM 2016-09-29 EPDS002 < MRL 0.005 MG/L .1 MG/L 2016-01-01
2018-12-31
6092563-01I 1024 CYANIDE 2016-09-29 EPDS002 < MRL 0.01 MG/L .2 MG/L 2016-01-01
2018-12-31
6092563-01I 1025 FLUORIDE 2016-09-29 EPDS002 < MRL 0.1 MG/L 4 MG/L 2016-01-01
2018-12-31
6092563-01I 1035 MERCURY 2016-09-29 EPDS002 < MRL 0.0002 MG/L .002 MG/L 2016-01-01
2018-12-31
6092563-01I 1036 NICKEL 2016-09-29 EPDS002 < MRL 0.02 MG/L 2016-01-01
2018-12-31
6092563-01I 1045 SELENIUM 2016-09-29 EPDS002 < MRL 0.002 MG/L .05 MG/L 2016-01-01
2018-12-31
6092563-01I 1085 THALLIUM, TOTAL 2016-09-29 EPDS002 < MRL 0.0005 MG/L .002 MG/L 2016-01-01
2018-12-31