ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0410144

Federal Type:

C

Water System Name:

GW- RINCON WATER COMPANY

Primary Source:

GW

Principal County Served:

PIMA

System Status:

A - MAP

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
DWC 132 1005 ARSENIC 1987-06-11 EPDS001 < MRL 0.01 MG/L .01 MG/L
DWC 132 1010 BARIUM 1987-06-11 EPDS001 < MRL 0.5 MG/L 2 MG/L
DWC 132 1015 CADMIUM 1987-06-11 EPDS001 < MRL 0.01 MG/L .005 MG/L
DWC 132 1017 CHLORIDE 1987-06-11 EPDS001 40.5  MG/L 250 MG/L
DWC 132 1020 CHROMIUM 1987-06-11 EPDS001 < MRL 0.05 MG/L .1 MG/L
DWC 132 1022 COPPER, FREE 1987-06-11 EPDS001 < MRL 0.05 MG/L 1.3 MG/L
DWC 132 1025 FLUORIDE 1987-06-11 EPDS001 < MRL 0.2 MG/L 4 MG/L
DWC 132 1028 IRON 1987-06-11 EPDS001 6.7  MG/L .3 MG/L
DWC 132 1030 LEAD 1987-06-11 EPDS001 < MRL 0.01 MG/L
DWC 132 1032 MANGANESE 1987-06-11 EPDS001 .23  MG/L .05 MG/L
DWC 132 1035 MERCURY 1987-06-11 EPDS001 < MRL 0.001 MG/L .002 MG/L
DWC 132 1040 NITRATE 1987-06-11 EPDS001 .2  MG/L 10 MG/L
DWC 132 1045 SELENIUM 1987-06-11 EPDS001 < MRL 0.005 MG/L .05 MG/L
DWC 132 1050 SILVER 1987-06-11 EPDS001 < MRL 0.025 MG/L .1 MG/L
DWC 132 1052 SODIUM 1987-06-11 EPDS001 104.1  MG/L 3000 MG/L
DWC 132 1055 SULFATE 1987-06-11 EPDS001 184.6  MG/L 250 MG/L
DWC 132 1095 ZINC 1987-06-11 EPDS001 .3  MG/L 5 MG/L