ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0410095

Federal Type:

C

Water System Name:

RAY WATER COMPANY INC

Primary Source:

GW

Principal County Served:

PIMA

System Status:

A - MAP

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
19898-04 1010 BARIUM 1994-05-16 EPDS004 .055  MG/L 2 MG/L
19898-04 1015 CADMIUM 1994-05-16 EPDS004 .003  MG/L .005 MG/L
19898-04 1017 CHLORIDE 1994-05-16 EPDS004 14  MG/L 250 MG/L
19898-04 1020 CHROMIUM 1994-05-16 EPDS004 .027  MG/L .1 MG/L
19898-04 1022 COPPER, FREE 1994-05-16 EPDS004 .002  MG/L 1.3 MG/L
19898-04 1025 FLUORIDE 1994-05-16 EPDS004 .4  MG/L 4 MG/L
19898-04 1028 IRON 1994-05-16 EPDS004 .02  MG/L .3 MG/L
19898-04 1030 LEAD 1994-05-16 EPDS004 .001  MG/L
19898-04 1032 MANGANESE 1994-05-16 EPDS004 .005  MG/L .05 MG/L
19898-04 1035 MERCURY 1994-05-16 EPDS004 .0001  MG/L .002 MG/L
19898-04 1040 NITRATE 1994-05-16 EPDS004 .45  MG/L 10 MG/L
19898-04 1041 NITRITE 1994-05-16 EPDS004 .002  MG/L 1 MG/L
19898-04 1045 SELENIUM 1994-05-16 EPDS004 .002  MG/L .05 MG/L
19898-04 1050 SILVER 1994-05-16 EPDS004 .01  MG/L .1 MG/L
19898-04 1052 SODIUM 1994-05-16 EPDS004 56.3  MG/L 3000 MG/L
19898-04 1055 SULFATE 1994-05-16 EPDS004 143  MG/L 250 MG/L
19898-04 1095 ZINC 1994-05-16 EPDS004 .01  MG/L 5 MG/L