ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0410095

Federal Type:

C

Water System Name:

RAY WATER COMPANY INC

Primary Source:

GW

Principal County Served:

PIMA

System Status:

A - MAP

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
19898-02 1010 BARIUM 1994-05-16 EPDS002 .054  MG/L 2 MG/L
19898-02 1015 CADMIUM 1994-05-16 EPDS002 < MRL 0.003 MG/L .005 MG/L
19898-02 1017 CHLORIDE 1994-05-16 EPDS002 9  MG/L 250 MG/L
19898-02 1020 CHROMIUM 1994-05-16 EPDS002 < MRL 0.006 MG/L .1 MG/L
19898-02 1022 COPPER, FREE 1994-05-16 EPDS002 .012  MG/L 1.3 MG/L
19898-02 1025 FLUORIDE 1994-05-16 EPDS002 .24  MG/L 4 MG/L
19898-02 1028 IRON 1994-05-16 EPDS002 .325  MG/L .3 MG/L
19898-02 1030 LEAD 1994-05-16 EPDS002 .0014  MG/L
19898-02 1032 MANGANESE 1994-05-16 EPDS002 .015  MG/L .05 MG/L
19898-02 1035 MERCURY 1994-05-16 EPDS002 < MRL 0.0001 MG/L .002 MG/L
19898-02 1040 NITRATE 1994-05-16 EPDS002 .56  MG/L 10 MG/L
19898-02 1041 NITRITE 1994-05-16 EPDS002 .002  MG/L 1 MG/L
19898-02 1045 SELENIUM 1994-05-16 EPDS002 < MRL 0.002 MG/L .05 MG/L
19898-02 1050 SILVER 1994-05-16 EPDS002 < MRL 0.01 MG/L .1 MG/L
19898-02 1052 SODIUM 1994-05-16 EPDS002 36.9  MG/L 3000 MG/L
19898-02 1055 SULFATE 1994-05-16 EPDS002 162  MG/L 250 MG/L
19898-02 1095 ZINC 1994-05-16 EPDS002 .015  MG/L 5 MG/L