ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0410046

Federal Type:

C

Water System Name:

METROPOLITAN DWID - E&T SYSTEM

Primary Source:

GW

Principal County Served:

PIMA

System Status:

A - MAP

Comments:

Activity Date:

1997-06-15



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
MAR97-08307 1074 ANTIMONY, TOTAL 1997-04-16 EPDS002 < MRL 0.003 MG/L .006 MG/L
MAR97-08307 1005 ARSENIC 1997-04-16 EPDS002 .0038  MG/L .01 MG/L
MAR97-08307 1010 BARIUM 1997-04-16 EPDS002 .096  MG/L 2 MG/L
MAR97-08307 1075 BERYLLIUM, TOTAL 1997-04-16 EPDS002 < MRL 0.0005 MG/L .004 MG/L
MAR97-08307 1015 CADMIUM 1997-04-16 EPDS002 < MRL 0.0005 MG/L .005 MG/L
MAR97-08307 1020 CHROMIUM 1997-04-16 EPDS002 < MRL 0.01 MG/L .1 MG/L
MAR97-08307 1024 CYANIDE 1997-04-16 EPDS002 < MRL 0.005 MG/L .2 MG/L
MAR97-08307 1025 FLUORIDE 1997-04-16 EPDS002 .34  MG/L 4 MG/L
MAR97-08307 1035 MERCURY 1997-04-16 EPDS002 < MRL 0.0002 MG/L .002 MG/L
MAR97-08307 1036 NICKEL 1997-04-16 EPDS002 < MRL 0.01 MG/L
MAR97-08307 1045 SELENIUM 1997-04-16 EPDS002 .0039  MG/L .05 MG/L
MAR97-08307 1085 THALLIUM, TOTAL 1997-04-16 EPDS002 < MRL 0.001 MG/L .002 MG/L