ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0402028

Federal Type:

C

Water System Name:

EAST SLOPE WATER COMPANY

Primary Source:

GW

Principal County Served:

COCHISE

System Status:

A - MAP

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
2602230021I 1074 ANTIMONY, TOTAL 2006-02-22 EPDS002 < MRL 0.001 MG/L .006 MG/L 2003-01-01
2011-12-31
2602230021I 1005 ARSENIC 2006-02-22 EPDS002 < MRL 0.001 MG/L .01 MG/L 2003-01-01
2011-12-31
2602230021I 1010 BARIUM 2006-02-22 EPDS002 .047  MG/L 2 MG/L 2003-01-01
2011-12-31
2602230021I 1075 BERYLLIUM, TOTAL 2006-02-22 EPDS002 < MRL 0.001 MG/L .004 MG/L 2003-01-01
2011-12-31
2602230021I 1015 CADMIUM 2006-02-22 EPDS002 < MRL 0.0005 MG/L .005 MG/L 2003-01-01
2011-12-31
2602230021I 1020 CHROMIUM 2006-02-22 EPDS002 .0013  MG/L .1 MG/L 2003-01-01
2011-12-31
2602230021I 1035 MERCURY 2006-02-22 EPDS002 < MRL 0.0002 MG/L .002 MG/L 2003-01-01
2011-12-31
2602230021I 1036 NICKEL 2006-02-22 EPDS002 < MRL 0.005 MG/L 2003-01-01
2011-12-31
2602230021I 1045 SELENIUM 2006-02-22 EPDS002 < MRL 0.005 MG/L .05 MG/L 2003-01-01
2011-12-31
2602230021I 1052 SODIUM 2006-02-22 EPDS002 8.4  MG/L 3000 MG/L 2003-01-01
2011-12-31
2602230021I 1085 THALLIUM, TOTAL 2006-02-22 EPDS002 < MRL 0.001 MG/L .002 MG/L 2003-01-01
2011-12-31