ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0409023

Federal Type:

C

Water System Name:

PONDEROSA DWID

Primary Source:

GW

Principal County Served:

NAVAJO

System Status:

A - MAP

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
122795-38 1074 ANTIMONY, TOTAL 1995-12-26 EPDS005 < MRL 0.003 MG/L .006 MG/L
122795-38 1005 ARSENIC 1995-12-26 EPDS005 < MRL 0.003 MG/L .01 MG/L
122795-38 1010 BARIUM 1995-12-26 EPDS005 < MRL 0.01 MG/L 2 MG/L
122795-38 1075 BERYLLIUM, TOTAL 1995-12-26 EPDS005 < MRL 0.0005 MG/L .004 MG/L
122795-38 1015 CADMIUM 1995-12-26 EPDS005 < MRL 0.0005 MG/L .005 MG/L
122795-38 1020 CHROMIUM 1995-12-26 EPDS005 < MRL 0.005 MG/L .1 MG/L
122795-38 1024 CYANIDE 1995-12-26 EPDS005 < MRL 0.005 MG/L .2 MG/L
122795-38 1025 FLUORIDE 1995-12-26 EPDS005 .04  MG/L 4 MG/L
122795-38 1035 MERCURY 1995-12-26 EPDS005 < MRL 0.0002 MG/L .002 MG/L
122795-38 1036 NICKEL 1995-12-26 EPDS005 < MRL 0.02 MG/L
122795-38 1038 NITRATE-NITRITE 1995-12-26 EPDS005 .17  MG/L 10 MG/L
122795-38 1045 SELENIUM 1995-12-26 EPDS005 < MRL 0.003 MG/L .05 MG/L