ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0408703

Federal Type:

NTNC

Water System Name:

NPS TEMPLE BAR WTP

Primary Source:

GW

Principal County Served:

MOHAVE

System Status:

A

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
951115071I 1074 ANTIMONY, TOTAL 1995-11-14 EPDS001 < MRL 0.001 MG/L .006 MG/L
951115071I 1005 ARSENIC 1995-11-14 EPDS001 .0013  MG/L .01 MG/L
951115071I 1094 ASBESTOS 1995-11-14 EPDS001 < MRL 0.09 MFL 7 MFL 1995-01-01
2003-12-31
951115071I 1010 BARIUM 1995-11-14 EPDS001 .028  MG/L 2 MG/L
951115071I 1075 BERYLLIUM, TOTAL 1995-11-14 EPDS001 < MRL 0.001 MG/L .004 MG/L
951115071I 1015 CADMIUM 1995-11-14 EPDS001 < MRL 0.0005 MG/L .005 MG/L
951115071I 1020 CHROMIUM 1995-11-14 EPDS001 .0045  MG/L .1 MG/L
951115071I 1024 CYANIDE 1995-11-14 EPDS001 < MRL 0.025 MG/L .2 MG/L
951115071I 1036 NICKEL 1995-11-14 EPDS001 < MRL 0.005 MG/L
951115071I 1045 SELENIUM 1995-11-14 EPDS001 < MRL 0.005 MG/L .05 MG/L
951115071I 1085 THALLIUM, TOTAL 1995-11-14 EPDS001 < MRL 0.001 MG/L .002 MG/L