ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0402014

Federal Type:

C

Water System Name:

DOUGLAS CITY OF

Primary Source:

GW

Principal County Served:

COCHISE

System Status:

A

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
19F1535-06 1074 ANTIMONY, TOTAL 2019-06-13 EPDS017 < MRL 0.0005 MG/L .006 MG/L 2019-01-01
2021-12-31
19F1535-06 1005 ARSENIC 2019-06-13 EPDS017 0.003  MG/L .01 MG/L 2019-01-01
2021-12-31
19F1535-06 1010 BARIUM 2019-06-13 EPDS017 0.088  MG/L 2 MG/L 2019-01-01
2021-12-31
19F1535-06 1075 BERYLLIUM, TOTAL 2019-06-13 EPDS017 < MRL 0.002 MG/L .004 MG/L 2019-01-01
2021-12-31
19F1535-06 1015 CADMIUM 2019-06-13 EPDS017 < MRL 0.0001 MG/L .005 MG/L 2019-01-01
2021-12-31
19F1535-06 1020 CHROMIUM 2019-06-13 EPDS017 0.005  MG/L .1 MG/L 2019-01-01
2021-12-31
19F1535-06 1024 CYANIDE 2019-06-13 EPDS017 < MRL 0.01 MG/L .2 MG/L 2019-01-01
2021-12-31
19F1535-06 1025 FLUORIDE 2019-06-13 EPDS017 0.42  MG/L 4 MG/L 2019-01-01
2021-12-31
19F1535-06 1035 MERCURY 2019-06-13 EPDS017 < MRL 0.0002 MG/L .002 MG/L 2019-01-01
2021-12-31
19F1535-06 1036 NICKEL 2019-06-13 EPDS017 < MRL 0.02 MG/L 2019-01-01
2021-12-31
19F1535-06 1045 SELENIUM 2019-06-13 EPDS017 < MRL 0.002 MG/L .05 MG/L 2019-01-01
2021-12-31
19F1535-06 1052 SODIUM 2019-06-13 EPDS017 130  MG/L 3000 MG/L 2019-01-01
2021-12-31
19F1535-06 1085 THALLIUM, TOTAL 2019-06-13 EPDS017 < MRL 0.0005 MG/L .002 MG/L 2019-01-01
2021-12-31