ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0402007

Federal Type:

C

Water System Name:

BELLA VISTA WATER SOUTH

Primary Source:

GW

Principal County Served:

COCHISE

System Status:

A - MAP

Comments:

Activity Date:

1955-01-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
94-06-74470 1005 ARSENIC 1994-06-17 EPDS006 < MRL 0.006 MG/L .01 MG/L
94-06-74470 1010 BARIUM 1994-06-17 EPDS006 < MRL 0.1 MG/L 2 MG/L
94-06-74470 1015 CADMIUM 1994-06-17 EPDS006 .009  MG/L .005 MG/L
94-06-74470 1017 CHLORIDE 1994-06-17 EPDS006 6.8  MG/L 250 MG/L
94-06-74470 1020 CHROMIUM 1994-06-17 EPDS006 .03  MG/L .1 MG/L
94-06-74470 1022 COPPER, FREE 1994-06-17 EPDS006 .018  MG/L 1.3 MG/L
94-06-74470 1025 FLUORIDE 1994-06-17 EPDS006 .17  MG/L 4 MG/L
94-06-74470 1028 IRON 1994-06-17 EPDS006 .04  MG/L .3 MG/L
94-06-74470 1030 LEAD 1994-06-17 EPDS006 < MRL 0.001 MG/L
94-06-74470 1032 MANGANESE 1994-06-17 EPDS006 .01  MG/L .05 MG/L
94-06-74470 1035 MERCURY 1994-06-17 EPDS006 < MRL 0.0002 MG/L .002 MG/L
94-06-74470 1040 NITRATE 1994-06-17 EPDS006 .58  MG/L 10 MG/L
94-06-74470 1045 SELENIUM 1994-06-17 EPDS006 < MRL 0.01 MG/L .05 MG/L
94-06-74470 1050 SILVER 1994-06-17 EPDS006 < MRL 0.01 MG/L .1 MG/L
94-06-74470 1052 SODIUM 1994-06-17 EPDS006 2.41  MG/L 3000 MG/L
94-06-74470 1055 SULFATE 1994-06-17 EPDS006 15.7  MG/L 250 MG/L
94-06-74470 1095 ZINC 1994-06-17 EPDS006 .84  MG/L 5 MG/L