ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0407695

Federal Type:

C

Water System Name:

EPCOR - AGUA FRIA

Primary Source:

SW

Principal County Served:

MARICOPA

System Status:

A

Comments:

Activity Date:

1986-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
CP18566 1074 ANTIMONY, TOTAL 2010-03-16 EPDS004 < MRL 0.0004 MG/L .006 MG/L 2008-01-01
2010-12-31
CP18566 1005 ARSENIC 2010-03-16 EPDS004 < MRL 0.001 MG/L .01 MG/L 2008-01-01
2010-12-31
CP18566 1010 BARIUM 2010-03-16 EPDS004 .118  MG/L 2 MG/L 2008-01-01
2010-12-31
CP18566 1075 BERYLLIUM, TOTAL 2010-03-16 EPDS004 < MRL 0.0003 MG/L .004 MG/L 2008-01-01
2010-12-31
CP18566 1015 CADMIUM 2010-03-16 EPDS004 < MRL 0.001 MG/L .005 MG/L 2008-01-01
2010-12-31
CP18566 1020 CHROMIUM 2010-03-16 EPDS004 < MRL 0.007 MG/L .1 MG/L 2008-01-01
2010-12-31
CP18566 1024 CYANIDE 2010-03-16 EPDS004 < MRL 0.005 MG/L .2 MG/L 2008-01-01
2010-12-31
CP18566 1025 FLUORIDE 2010-03-16 EPDS004 0.3  MG/L 4 MG/L 2008-01-01
2010-12-31
CP18566 1035 MERCURY 2010-03-16 EPDS004 < MRL 0.0002 MG/L .002 MG/L 2008-01-01
2010-12-31
CP18566 1036 NICKEL 2010-03-16 EPDS004 .0026  MG/L 2008-01-01
2010-12-31
CP18566 1045 SELENIUM 2010-03-16 EPDS004 < MRL 0.002 MG/L .05 MG/L 2008-01-01
2010-12-31
CP18566 1052 SODIUM 2010-03-16 EPDS004 94.2  MG/L 3000 MG/L 2008-01-01
2010-12-31
CP18566 1085 THALLIUM, TOTAL 2010-03-16 EPDS004 < MRL 0.0003 MG/L .002 MG/L 2008-01-01
2010-12-31