ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0407609

Federal Type:

NP

Water System Name:

RIGBY WATER COMPANY - CHILDERS

Primary Source:

GW

Principal County Served:

MARICOPA

System Status:

I

Comments:

Activity Date:

2008-03-24



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
BC-02333 1074 ANTIMONY, TOTAL 1997-03-20 EPDS001 < MRL 0.003 MG/L .006 MG/L
BC-02333 1005 ARSENIC 1997-03-20 EPDS001 < MRL 0.005 MG/L .01 MG/L
BC-02333 1010 BARIUM 1997-03-20 EPDS001 .04  MG/L 2 MG/L
BC-02333 1075 BERYLLIUM, TOTAL 1997-03-20 EPDS001 < MRL 0.002 MG/L .004 MG/L
BC-02333 1015 CADMIUM 1997-03-20 EPDS001 < MRL 0.002 MG/L .005 MG/L
BC-02333 1020 CHROMIUM 1997-03-20 EPDS001 < MRL 0.01 MG/L .1 MG/L
BC-02333 1024 CYANIDE 1997-03-20 EPDS001 < MRL 0.01 MG/L .2 MG/L
BC-02333 1025 FLUORIDE 1997-03-20 EPDS001 .2  MG/L 4 MG/L
BC-02333 1035 MERCURY 1997-03-20 EPDS001 < MRL 0.0002 MG/L .002 MG/L
BC-02333 1036 NICKEL 1997-03-20 EPDS001 < MRL 0.01 MG/L
BC-02333 1040 NITRATE 1997-03-20 EPDS001 2.64  MG/L 10 MG/L
BC-02333 1045 SELENIUM 1997-03-20 EPDS001 < MRL 0.005 MG/L .05 MG/L