ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0407504

Federal Type:

C

Water System Name:

EPCOR - ANTHEM

Primary Source:

SW

Principal County Served:

MARICOPA

System Status:

A

Comments:

Activity Date:

1999-01-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
051800-16 1074 ANTIMONY, TOTAL 2000-05-16 EPDS001 < MRL 0.003 MG/L .006 MG/L
051800-16 1005 ARSENIC 2000-05-16 EPDS001 .0038  MG/L .01 MG/L
051800-16 1010 BARIUM 2000-05-16 EPDS001 .098  MG/L 2 MG/L
051800-16 1075 BERYLLIUM, TOTAL 2000-05-16 EPDS001 < MRL 0.0005 MG/L .004 MG/L
051800-16 1015 CADMIUM 2000-05-16 EPDS001 < MRL 0.0005 MG/L .005 MG/L
051800-16 1020 CHROMIUM 2000-05-16 EPDS001 < MRL 0.01 MG/L .1 MG/L
051800-16 1024 CYANIDE 2000-05-16 EPDS001 < MRL 0.005 MG/L .2 MG/L
051800-16 1025 FLUORIDE 2000-05-16 EPDS001 .3  MG/L 4 MG/L
051800-16 1035 MERCURY 2000-05-16 EPDS001 < MRL 0.0002 MG/L .002 MG/L
051800-16 1045 SELENIUM 2000-05-16 EPDS001 < MRL 0.003 MG/L .05 MG/L