ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0407477

Federal Type:

NTNC

Water System Name:

PAI DOMESTIC

Primary Source:

GW

Principal County Served:

MARICOPA

System Status:

A - MAP

Comments:

Activity Date:

1987-04-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
9710-06449-1 I 1074 ANTIMONY, TOTAL 1997-10-06 EPDS001 < MRL 0.004 MG/L .006 MG/L
9710-06449-1 I 1005 ARSENIC 1997-10-06 EPDS001 .009  MG/L .01 MG/L
9710-06449-1 I 1010 BARIUM 1997-10-06 EPDS001 .03  MG/L 2 MG/L
9710-06449-1 I 1075 BERYLLIUM, TOTAL 1997-10-06 EPDS001 < MRL 0.002 MG/L .004 MG/L
9710-06449-1 I 1015 CADMIUM 1997-10-06 EPDS001 < MRL 0.001 MG/L .005 MG/L
9710-06449-1 I 1020 CHROMIUM 1997-10-06 EPDS001 .052  MG/L .1 MG/L
9710-06449-1 I 1025 FLUORIDE 1997-10-06 EPDS001 4.3  MG/L 4 MG/L
9710-06449-1 I 1035 MERCURY 1997-10-06 EPDS001 < MRL 0.0002 MG/L .002 MG/L
9710-06449-1 I 1036 NICKEL 1997-10-06 EPDS001 < MRL 0.02 MG/L
9710-06449-1 I 1045 SELENIUM 1997-10-06 EPDS001 < MRL 0.005 MG/L .05 MG/L
9710-06449-1 I 1085 THALLIUM, TOTAL 1997-10-06 EPDS001 .001  MG/L .002 MG/L