ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0407321

Federal Type:

NP

Water System Name:

STEWART MOUNTAIN DAM

Primary Source:

GW

Principal County Served:

MARICOPA

System Status:

I

Comments:

Activity Date:

2009-04-28



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
225-10I 1005 ARSENIC 1993-07-07 EPDS001 < MRL 0.004 MG/L .01 MG/L
225-10I 1010 BARIUM 1993-07-07 EPDS001 .01  MG/L 2 MG/L
225-10I 1015 CADMIUM 1993-07-07 EPDS001 < MRL 0.0002 MG/L .005 MG/L
225-10I 1017 CHLORIDE 1993-07-07 EPDS001 78.5  MG/L 250 MG/L
225-10I 1020 CHROMIUM 1993-07-07 EPDS001 < MRL 0.01 MG/L .1 MG/L
225-10I 1022 COPPER, FREE 1993-07-07 EPDS001 < MRL 0.01 MG/L 1.3 MG/L
225-10I 1025 FLUORIDE 1993-07-07 EPDS001 .27  MG/L 4 MG/L
225-10I 1028 IRON 1993-07-07 EPDS001 .049  MG/L .3 MG/L
225-10I 1030 LEAD 1993-07-07 EPDS001 .002  MG/L
225-10I 1032 MANGANESE 1993-07-07 EPDS001 < MRL 0.01 MG/L .05 MG/L
225-10I 1035 MERCURY 1993-07-07 EPDS001 < MRL 0.0002 MG/L .002 MG/L
225-10I 1040 NITRATE 1993-07-07 EPDS001 < MRL 0.4 MG/L 10 MG/L
225-10I 1045 SELENIUM 1993-07-07 EPDS001 < MRL 0.002 MG/L .05 MG/L
225-10I 1050 SILVER 1993-07-07 EPDS001 < MRL 0.01 MG/L .1 MG/L
225-10I 1052 SODIUM 1993-07-07 EPDS001 71.2  MG/L 3000 MG/L
225-10I 1055 SULFATE 1993-07-07 EPDS001 44.3  MG/L 250 MG/L
225-10I 1095 ZINC 1993-07-07 EPDS001 .037  MG/L 5 MG/L