ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0407167

Federal Type:

C

Water System Name:

WEST END WATER COMPANY - WHEAT

Primary Source:

GW

Principal County Served:

MARICOPA

System Status:

A - MAP

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
981113219I 1074 ANTIMONY, TOTAL 1998-11-11 EPDS001 < MRL 0.001 MG/L .006 MG/L
981113219I 1005 ARSENIC 1998-11-11 EPDS001 .0035  MG/L .01 MG/L
981113219I 1010 BARIUM 1998-11-11 EPDS001 .071  MG/L 2 MG/L
981113219I 1075 BERYLLIUM, TOTAL 1998-11-11 EPDS001 < MRL 0.001 MG/L .004 MG/L
981113219I 1015 CADMIUM 1998-11-11 EPDS001 < MRL 0.0005 MG/L .005 MG/L
981113219I 1020 CHROMIUM 1998-11-11 EPDS001 .013  MG/L .1 MG/L
981113219I 1024 CYANIDE 1998-11-11 EPDS001 < MRL 0.03 MG/L .2 MG/L
981113219I 1025 FLUORIDE 1998-11-11 EPDS001 .49  MG/L 4 MG/L
981113219I 1035 MERCURY 1998-11-11 EPDS001 < MRL 0.0002 MG/L .002 MG/L
981113219I 1036 NICKEL 1998-11-11 EPDS001 < MRL 0.005 MG/L
981113219I 1045 SELENIUM 1998-11-11 EPDS001 < MRL 0.005 MG/L .05 MG/L
981113219I 1052 SODIUM 1998-11-11 EPDS001 39  MG/L 3000 MG/L
981113219I 1055 SULFATE 1998-11-11 EPDS001 24  MG/L 250 MG/L