ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0407099

Federal Type:

C

Water System Name:

EPCOR - SUN CITY

Primary Source:

GW

Principal County Served:

MARICOPA

System Status:

A

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
CN70193 1074 ANTIMONY, TOTAL 2009-09-15 EPDS006W < MRL 0.0004 MG/L .006 MG/L 2009-01-01
2011-12-31
CN70193 1005 ARSENIC 2009-09-15 EPDS006W .007  MG/L .01 MG/L 2009-01-01
2011-12-31
CN70193 1010 BARIUM 2009-09-15 EPDS006W .021  MG/L 2 MG/L 2009-01-01
2011-12-31
CN70193 1075 BERYLLIUM, TOTAL 2009-09-15 EPDS006W < MRL 0.0003 MG/L .004 MG/L 2009-01-01
2011-12-31
CN70193 1015 CADMIUM 2009-09-15 EPDS006W < MRL 0.001 MG/L .005 MG/L 2009-01-01
2011-12-31
CN70193 1020 CHROMIUM 2009-09-15 EPDS006W .012  MG/L .1 MG/L 2009-01-01
2011-12-31
CN70193 1035 MERCURY 2009-09-15 EPDS006W < MRL 0.0002 MG/L .002 MG/L 2009-01-01
2011-12-31
CN70193 1036 NICKEL 2009-09-15 EPDS006W .0011  MG/L 2009-01-01
2011-12-31
CN70193 1045 SELENIUM 2009-09-15 EPDS006W < MRL 0.002 MG/L .05 MG/L 2009-01-01
2011-12-31
CN70193 1052 SODIUM 2009-09-15 EPDS006W 55  MG/L 3000 MG/L 2009-01-01
2011-12-31
CN70193 1085 THALLIUM, TOTAL 2009-09-15 EPDS006W < MRL 0.0003 MG/L .002 MG/L 2009-01-01
2011-12-31