ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0407098

Federal Type:

C

Water System Name:

SCOTTSDALE CITY OF

Primary Source:

SW

Principal County Served:

MARICOPA

System Status:

A

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
AC18353 1074 ANTIMONY, TOTAL 2022-02-24 EPDS232 < MRL 0.001 MG/L .006 MG/L 2022-01-01
2022-12-31
AC18353 1005 ARSENIC 2022-02-24 EPDS232 0.0046  MG/L .01 MG/L 2022-01-01
2022-03-31
AC18353 1010 BARIUM 2022-02-24 EPDS232 0.0335  MG/L 2 MG/L 2022-01-01
2022-12-31
AC18353 1075 BERYLLIUM, TOTAL 2022-02-24 EPDS232 < MRL 0.001 MG/L .004 MG/L 2022-01-01
2022-12-31
AC18353 1015 CADMIUM 2022-02-24 EPDS232 < MRL 0.001 MG/L .005 MG/L 2022-01-01
2022-12-31
AC18353 1020 CHROMIUM 2022-02-24 EPDS232 0.0181  MG/L .1 MG/L 2022-01-01
2022-12-31
AC18353 1025 FLUORIDE 2022-02-24 EPDS232 0.4  MG/L 4 MG/L 2022-01-01
2022-12-31
AC18353 1035 MERCURY 2022-02-24 EPDS232 < MRL 0.0001 MG/L .002 MG/L 2022-01-01
2022-12-31
AC18353 1036 NICKEL 2022-02-24 EPDS232 < MRL 0.001 MG/L 2022-01-01
2022-12-31
AC18353 1040 NITRATE 2022-02-24 EPDS232 0.7  MG/L 10 MG/L 2022-01-01
2022-12-31
AC18353 1038 NITRATE-NITRITE 2022-02-24 EPDS232 0.7  MG/L 10 MG/L
AC18353 1041 NITRITE 2022-02-24 EPDS232 < MRL 0.2 MG/L 1 MG/L 2017-01-01
2025-12-31
AC18353 1045 SELENIUM 2022-02-24 EPDS232 0.0010  MG/L .05 MG/L 2022-01-01
2022-12-31
AC18353 1052 SODIUM 2022-02-24 EPDS232 51  MG/L 3000 MG/L 2022-01-01
2022-12-31
AC18353 1085 THALLIUM, TOTAL 2022-02-24 EPDS232 < MRL 0.001 MG/L .002 MG/L 2022-01-01
2022-12-31