ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0407098

Federal Type:

C

Water System Name:

SCOTTSDALE CITY OF

Primary Source:

SW

Principal County Served:

MARICOPA

System Status:

A

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
AB03907I 1074 ANTIMONY, TOTAL 2009-01-22 EPDS001 < MRL 0.002 MG/L .006 MG/L 2009-01-01
2009-12-31
AB03907I 1005 ARSENIC 2009-01-22 EPDS001 < MRL 0.001 MG/L .01 MG/L 2009-01-01
2009-12-31
AB03907I 1010 BARIUM 2009-01-22 EPDS001 0.141  MG/L 2 MG/L 2009-01-01
2009-12-31
AB03907I 1075 BERYLLIUM, TOTAL 2009-01-22 EPDS001 < MRL 0.002 MG/L .004 MG/L 2009-01-01
2009-12-31
AB03907I 1015 CADMIUM 2009-01-22 EPDS001 < MRL 0.002 MG/L .005 MG/L 2009-01-01
2009-12-31
AB03907I 1020 CHROMIUM 2009-01-22 EPDS001 < MRL 0.01 MG/L .1 MG/L 2009-01-01
2009-12-31
AB03907I 1025 FLUORIDE 2009-01-22 EPDS001 0.3  MG/L 4 MG/L 2009-01-01
2009-12-31
AB03907I 1036 NICKEL 2009-01-22 EPDS001 < MRL 0.01 MG/L 2009-01-01
2009-12-31
AB03907I 1040 NITRATE 2009-01-22 EPDS001 0.4  MG/L 10 MG/L 2009-01-01
2009-12-31
AB03907I 1045 SELENIUM 2009-01-22 EPDS001 < MRL 0.002 MG/L .05 MG/L 2009-01-01
2009-12-31
AB03907I 1052 SODIUM 2009-01-22 EPDS001 100  MG/L 3000 MG/L 2009-01-01
2009-12-31
AB03907I 1085 THALLIUM, TOTAL 2009-01-22 EPDS001 < MRL 0.001 MG/L .002 MG/L 2009-01-01
2009-12-31