ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0407096

Federal Type:

C

Water System Name:

PEORIA CITY OF

Primary Source:

SW

Principal County Served:

MARICOPA

System Status:

A

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
22G0348-07 2943 BROMODICHLOROMETHANE 2022-07-05 04-A 0.0217  MG/L .1 MG/L
22G0348-07 2942 BROMOFORM 2022-07-05 04-A 0.0088  MG/L .1 MG/L
22G0348-07 2941 CHLOROFORM 2022-07-05 04-A 0.0172  MG/L .1 MG/L
22G0348-07 2944 DIBROMOCHLOROMETHANE 2022-07-05 04-A 0.0269  MG/L .1 MG/L
22G0348-07 2456 TOTAL HALOACETIC ACIDS (HAA5) 2022-07-05 04-A 0.016  MG/L .06 MG/L 2022-07-01
2022-09-30
22G0348-07 2950 TTHM 2022-07-05 04-A 0.0746  MG/L .08 MG/L 2022-07-01
2022-09-30