ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0407094

Federal Type:

C

Water System Name:

GOODYEAR WATER DEPARTMENT

Primary Source:

SW

Principal County Served:

MARICOPA

System Status:

A

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
2104300042I 1074 ANTIMONY, TOTAL 2001-04-27 EPDS010 < MRL 0.001 MG/L .006 MG/L 2001-01-01
2003-12-31
2104300042I 1005 ARSENIC 2001-04-27 EPDS010 .0075  MG/L .01 MG/L 2001-01-01
2003-12-31
2104300042I 1010 BARIUM 2001-04-27 EPDS010 .1  MG/L 2 MG/L 2001-01-01
2003-12-31
2104300042I 1075 BERYLLIUM, TOTAL 2001-04-27 EPDS010 < MRL 0.001 MG/L .004 MG/L 2001-01-01
2003-12-31
2104300042I 1015 CADMIUM 2001-04-27 EPDS010 < MRL 0.0005 MG/L .005 MG/L 2001-01-01
2003-12-31
2104300042I 1020 CHROMIUM 2001-04-27 EPDS010 .011  MG/L .1 MG/L 2001-01-01
2003-12-31
2104300042I 1024 CYANIDE 2001-04-27 EPDS010 < MRL 0.03 MG/L .2 MG/L 2001-01-01
2003-12-31
2104300042I 1025 FLUORIDE 2001-04-27 EPDS010 .55  MG/L 4 MG/L 2001-01-01
2003-12-31
2104300042I 1035 MERCURY 2001-04-27 EPDS010 < MRL 0.0002 MG/L .002 MG/L 2001-01-01
2003-12-31
2104300042I 1045 SELENIUM 2001-04-27 EPDS010 < MRL 0.02 MG/L .05 MG/L 2001-01-01
2003-12-31
2104300042I 1085 THALLIUM, TOTAL 2001-04-27 EPDS010 < MRL 0.001 MG/L .002 MG/L 2001-01-01
2003-12-31