ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0407094

Federal Type:

C

Water System Name:

GOODYEAR WATER DEPARTMENT

Primary Source:

SW

Principal County Served:

MARICOPA

System Status:

A

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
23C1312-02IOC 1074 ANTIMONY, TOTAL 2023-03-09 EPDS011 < MRL 0.002 MG/L .006 MG/L 2023-01-01
2023-12-31
23C1312-02IOC 1005 ARSENIC 2023-03-09 EPDS011 .0053  MG/L .01 MG/L 2023-01-01
2023-12-31
23C1312-02IOC 1010 BARIUM 2023-03-09 EPDS011 .05  MG/L 2 MG/L 2023-01-01
2023-12-31
23C1312-02IOC 1075 BERYLLIUM, TOTAL 2023-03-09 EPDS011 < MRL 0.002 MG/L .004 MG/L 2023-01-01
2023-12-31
23C1312-02IOC 1015 CADMIUM 2023-03-09 EPDS011 < MRL 0.0004 MG/L .005 MG/L 2023-01-01
2023-12-31
23C1312-02IOC 1020 CHROMIUM 2023-03-09 EPDS011 .012  MG/L .1 MG/L 2023-01-01
2023-12-31
23C1312-02IOC 1025 FLUORIDE 2023-03-09 EPDS011 < MRL 0.5 MG/L 4 MG/L 2023-01-01
2023-12-31
23C1312-02IOC 1035 MERCURY 2023-03-09 EPDS011 < MRL 0.0002 MG/L .002 MG/L 2023-01-01
2023-12-31
23C1312-02IOC 1036 NICKEL 2023-03-09 EPDS011 < MRL 0.02 MG/L 2023-01-01
2023-12-31
23C1312-02IOC 1040 NITRATE 2023-03-09 EPDS011 6.12  MG/L 10 MG/L 2023-01-01
2023-03-31
23C1312-02IOC 1038 NITRATE-NITRITE 2023-03-09 EPDS011 6.12  MG/L 10 MG/L
23C1312-02IOC 1041 NITRITE 2023-03-09 EPDS011 < MRL 0.25 MG/L 1 MG/L 2019-01-01
2027-12-31
23C1312-02IOC 1045 SELENIUM 2023-03-09 EPDS011 < MRL 0.008 MG/L .05 MG/L 2023-01-01
2023-12-31
23C1312-02IOC 1052 SODIUM 2023-03-09 EPDS011 140  MG/L 3000 MG/L 2023-01-01
2023-12-31
23C1312-02IOC 1085 THALLIUM, TOTAL 2023-03-09 EPDS011 < MRL 0.002 MG/L .002 MG/L 2023-01-01
2023-12-31