ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0407094

Federal Type:

C

Water System Name:

GOODYEAR WATER DEPARTMENT

Primary Source:

SW

Principal County Served:

MARICOPA

System Status:

A

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
202102180249I 1074 ANTIMONY, TOTAL 2021-02-17 EPDS003 < MRL 0.001 MG/L .006 MG/L 2019-01-01
2021-12-31
202102180249I 1005 ARSENIC 2021-02-17 EPDS003 0.0042  MG/L .01 MG/L 2019-01-01
2021-12-31
202102180249I 1010 BARIUM 2021-02-17 EPDS003 0.21  MG/L 2 MG/L 2019-01-01
2021-12-31
202102180249I 1075 BERYLLIUM, TOTAL 2021-02-17 EPDS003 < MRL 0.001 MG/L .004 MG/L 2019-01-01
2021-12-31
202102180249I 1015 CADMIUM 2021-02-17 EPDS003 < MRL 0.0005 MG/L .005 MG/L 2019-01-01
2021-12-31
202102180249I 1020 CHROMIUM 2021-02-17 EPDS003 0.0084  MG/L .1 MG/L 2019-01-01
2021-12-31
202102180249I 1024 CYANIDE 2021-02-17 EPDS003 < MRL 0.0025 MG/L .2 MG/L 2019-01-01
2021-12-31
202102180249I 1025 FLUORIDE 2021-02-17 EPDS003 0.19  MG/L 4 MG/L 2019-01-01
2021-12-31
202102180249I 1035 MERCURY 2021-02-17 EPDS003 < MRL 0.0002 MG/L .002 MG/L 2019-01-01
2021-12-31
202102180249I 1036 NICKEL 2021-02-17 EPDS003 < MRL 0.005 MG/L 2019-01-01
2021-12-31
202102180249I 1040 NITRATE 2021-02-17 EPDS003 9.6  MG/L 10 MG/L 2021-01-01
2021-03-31
202102180249I 1038 NITRATE-NITRITE 2021-02-17 EPDS003 9.6  MG/L 10 MG/L
202102180249I 1041 NITRITE 2021-02-17 EPDS003 < MRL 0.05 MG/L 1 MG/L 2013-01-01
2021-12-31
202102180249I 1045 SELENIUM 2021-02-17 EPDS003 < MRL 0.005 MG/L .05 MG/L 2019-01-01
2021-12-31
202102180249I 1052 SODIUM 2021-02-17 EPDS003 82  MG/L 3000 MG/L 2019-01-01
2021-12-31
202102180249I 1085 THALLIUM, TOTAL 2021-02-17 EPDS003 < MDL 0.001 MG/L .002 MG/L 2019-01-01
2021-12-31