ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0407093

Federal Type:

C

Water System Name:

GLENDALE CITY OF

Primary Source:

SW

Principal County Served:

MARICOPA

System Status:

A

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
2310181200W43FI 1005 ARSENIC 2023-10-18 EPDS043 < MRL 0.0025 MG/L .01 MG/L 2020-01-01
2028-12-31
2310181200W43FI 1010 BARIUM 2023-10-18 EPDS043 .07  MG/L 2 MG/L 2020-01-01
2028-12-31
2310181200W43FI 1075 BERYLLIUM, TOTAL 2023-10-18 EPDS043 < MRL 0.001 MG/L .004 MG/L 2020-01-01
2028-12-31
2310181200W43FI 1015 CADMIUM 2023-10-18 EPDS043 < MRL 0.001 MG/L .005 MG/L 2020-01-01
2028-12-31
2310181200W43FI 1020 CHROMIUM 2023-10-18 EPDS043 .003  MG/L .1 MG/L 2020-01-01
2028-12-31
2310181200W43FI 1025 FLUORIDE 2023-10-18 EPDS043 < MRL 0.3 MG/L 4 MG/L 2020-01-01
2028-12-31
2310181200W43FI 1036 NICKEL 2023-10-18 EPDS043 < MRL 0.005 MG/L 2020-01-01
2028-12-31
2310181200W43FI 1040 NITRATE 2023-10-18 EPDS043 3.18  MG/L 10 MG/L 2023-01-01
2023-12-31
2310181200W43FI 1038 NITRATE-NITRITE 2023-10-18 EPDS043 3.18  MG/L 10 MG/L
2310181200W43FI 1041 NITRITE 2023-10-18 EPDS043 < MRL 0.2 MG/L 1 MG/L 2017-01-01
2025-12-31
2310181200W43FI 1045 SELENIUM 2023-10-18 EPDS043 < MRL 0.01 MG/L .05 MG/L 2020-01-01
2028-12-31
2310181200W43FI 1052 SODIUM 2023-10-18 EPDS043 157  MG/L 3000 MG/L 2023-01-01
2023-12-31