ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0407090

Federal Type:

C

Water System Name:

CHANDLER CITY OF

Primary Source:

SW

Principal County Served:

MARICOPA

System Status:

A

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
PLA0102-13I 1074 ANTIMONY, TOTAL 2002-01-09 EPDS004 < MRL 0.004 MG/L .006 MG/L 2002-01-01
2002-12-31
PLA0102-13I 1005 ARSENIC 2002-01-09 EPDS004 < MRL 0.003 MG/L .01 MG/L 2002-01-01
2002-12-31
PLA0102-13I 1010 BARIUM 2002-01-09 EPDS004 .081  MG/L 2 MG/L 2002-01-01
2002-12-31
PLA0102-13I 1075 BERYLLIUM, TOTAL 2002-01-09 EPDS004 < MRL 0.004 MG/L .004 MG/L 2002-01-01
2002-12-31
PLA0102-13I 1015 CADMIUM 2002-01-09 EPDS004 < MRL 0.005 MG/L .005 MG/L 2002-01-01
2002-12-31
PLA0102-13I 1020 CHROMIUM 2002-01-09 EPDS004 < MRL 0.004 MG/L .1 MG/L 2002-01-01
2002-12-31
PLA0102-13I 1024 CYANIDE 2002-01-09 EPDS004 < MRL 0.02 MG/L .2 MG/L 2002-01-01
2002-12-31
PLA0102-13I 1025 FLUORIDE 2002-01-09 EPDS004 < MRL 1 MG/L 4 MG/L 2002-01-01
2002-12-31
PLA0102-13I 1035 MERCURY 2002-01-09 EPDS004 < MRL 0.0002 MG/L .002 MG/L 2002-01-01
2002-12-31
PLA0102-13I 1036 NICKEL 2002-01-09 EPDS004 < MRL 0.05 MG/L 2002-01-01
2002-12-31
PLA0102-13I 1040 NITRATE 2002-01-09 EPDS004 2.3  MG/L 10 MG/L 2002-01-01
2002-12-31
PLA0102-13I 1038 NITRATE-NITRITE 2002-01-09 EPDS004 2.3  MG/L 10 MG/L
PLA0102-13I 1041 NITRITE 2002-01-09 EPDS004 < MRL 1 MG/L 1 MG/L
PLA0102-13I 1045 SELENIUM 2002-01-09 EPDS004 < MRL 0.004 MG/L .05 MG/L 2002-01-01
2002-12-31
PLA0102-13I 1052 SODIUM 2002-01-09 EPDS004 200  MG/L 3000 MG/L 2002-01-01
2002-12-31
PLA0102-13I 1055 SULFATE 2002-01-09 EPDS004 130  MG/L 250 MG/L
PLA0102-13I 1085 THALLIUM, TOTAL 2002-01-09 EPDS004 < MRL 0.002 MG/L .002 MG/L 2002-01-01
2002-12-31