ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0407090

Federal Type:

C

Water System Name:

CHANDLER CITY OF

Primary Source:

SW

Principal County Served:

MARICOPA

System Status:

A

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
550-177269-4 IOC 1074 ANTIMONY, TOTAL 2022-01-13 EPDS016 < MRL 0.0016 MG/L .006 MG/L 2022-01-01
2022-12-31
550-177269-4 IOC 1005 ARSENIC 2022-01-13 EPDS016 0.0068  MG/L .01 MG/L 2022-01-01
2022-12-31
550-177269-4 IOC 1010 BARIUM 2022-01-13 EPDS016 0.057  MG/L 2 MG/L 2022-01-01
2022-12-31
550-177269-4 IOC 1075 BERYLLIUM, TOTAL 2022-01-13 EPDS016 < MRL 0.0004 MG/L .004 MG/L 2022-01-01
2022-12-31
550-177269-4 IOC 1015 CADMIUM 2022-01-13 EPDS016 < MRL 0.0001 MG/L .005 MG/L 2022-01-01
2022-12-31
550-177269-4 IOC 1020 CHROMIUM 2022-01-13 EPDS016 0.015  MG/L .1 MG/L 2022-01-01
2022-12-31
550-177269-4 IOC 1024 CYANIDE 2022-01-13 EPDS016 < MRL 0.05 MG/L .2 MG/L 2022-01-01
2022-12-31
550-177269-4 IOC 1025 FLUORIDE 2022-01-13 EPDS016 0.60  MG/L 4 MG/L 2022-01-01
2022-12-31
550-177269-4 IOC 1035 MERCURY 2022-01-13 EPDS016 < MRL 0.0002 MG/L .002 MG/L 2022-01-01
2022-12-31
550-177269-4 IOC 1036 NICKEL 2022-01-13 EPDS016 < MRL 0.002 MG/L 2022-01-01
2022-12-31
550-177269-4 IOC 1040 NITRATE 2022-01-13 EPDS016 6.2  MG/L 10 MG/L 2022-01-01
2022-03-31
550-177269-4 IOC 1038 NITRATE-NITRITE 2022-01-13 EPDS016 6.2  MG/L 10 MG/L
550-177269-4 IOC 1041 NITRITE 2022-01-13 EPDS016 < MRL 0.05 MG/L 1 MG/L 2021-01-01
2029-12-31
550-177269-4 IOC 1045 SELENIUM 2022-01-13 EPDS016 0.0016  MG/L .05 MG/L 2022-01-01
2022-12-31
550-177269-4 IOC 1052 SODIUM 2022-01-13 EPDS016 210  MG/L 3000 MG/L 2022-01-01
2022-12-31
550-177269-4 IOC 1085 THALLIUM, TOTAL 2022-01-13 EPDS016 < MRL 0.0001 MG/L .002 MG/L 2022-01-01
2022-12-31