ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0407069

Federal Type:

C

Water System Name:

GILA BEND TOWN OF

Primary Source:

GW

Principal County Served:

MARICOPA

System Status:

A - MAP

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
202202080150I 1074 ANTIMONY, TOTAL 2022-02-07 EPDS003 < MRL 1 UG/L .006 MG/L 2022-01-01
2024-12-31
202202080150I 1005 ARSENIC 2022-02-07 EPDS003 2  UG/L .01 MG/L 2022-01-01
2022-03-31
202202080150I 1010 BARIUM 2022-02-07 EPDS003 9.2  UG/L 2 MG/L 2022-01-01
2024-12-31
202202080150I 1075 BERYLLIUM, TOTAL 2022-02-07 EPDS003 < MRL 1 UG/L .004 MG/L 2022-01-01
2024-12-31
202202080150I 1015 CADMIUM 2022-02-07 EPDS003 < MRL 0.5 UG/L .005 MG/L 2022-01-01
2024-12-31
202202080150I 1020 CHROMIUM 2022-02-07 EPDS003 6  UG/L .1 MG/L 2022-01-01
2024-12-31
202202080150I 1024 CYANIDE 2022-02-07 EPDS003 < MRL 0.025 MG/L .2 MG/L 2022-01-01
2024-12-31
202202080150I 1025 FLUORIDE 2022-02-07 EPDS003 1.7  MG/L 4 MG/L 2022-01-01
2022-03-31
202202080150I 1035 MERCURY 2022-02-07 EPDS003 < MRL 0.2 UG/L .002 MG/L 2022-01-01
2024-12-31
202202080150I 1036 NICKEL 2022-02-07 EPDS003 < MRL 5 UG/L 2022-01-01
2024-12-31
202202080150I 1045 SELENIUM 2022-02-07 EPDS003 < MRL 5 UG/L .05 MG/L 2022-01-01
2024-12-31
202202080150I 1052 SODIUM 2022-02-07 EPDS003 110  MG/L 3000 MG/L 2022-01-01
2024-12-31
202202080150I 1085 THALLIUM, TOTAL 2022-02-07 EPDS003 < MRL 1 UG/L .002 MG/L 2022-01-01
2024-12-31